3 digital setpoints via frequency input, Digital setpoints via frequency input, Function library – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 110
![background image](/manuals/566255/110/background.png)
Function library
Configuration of analog and digital setpoints and actual values
7−39
L
EDB82MV752 EN 5.2
7.6.3
Digital setpoints via frequency input
Description
It is possible to configure the digital inputs E1 and E2 of the standard I/O or application I/O as
frequency input. This enables you to select a digital frequency as setpoint or actual value:
·
For operation with standard I/O
– single−tracked: 0 ... 10 kHz at X3/E1
– two−tracked: 0 ... 1 kHz at X3/E1 and X3/E2
·
For operation with application I/O
– single−tracked: 0 ... 100 kHz at X3/E1
– two−tracked: 0 ...100 kHz at X3/E1 and X3/E2
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0425*
v
Configuration
frequency input
single track X3/E1
(DFIN1)
2
f
r
Df
min
t
f
max
·
f
r
= Normalisation frequency
– f
r
corresponds to C0011
·
Df
min
= Resolution
·
t = Scanning rate
– The lower the scanning rate the
higher the dynamic response.
·
f
max
= Maximum frequency which can
be processed independently of C0425
– Set C0425 that the frequency coming
from the encoder is lower than f
max
·
Activate frequency input with
C0410/24 = 1
·
Adjust frequency input under C0426 and
C0427
^ 7−39
0
100 Hz
1/200
1 s
300 Hz
1
1 kHz
1/200
100 msec
3 kHz
2
10 kHz
1/200
10 msec
10 kHz
3
10 kHz
1/1000
50 msec
10 kHz
4
10 kHz
1/10000
500 ms
10 kHz
5 (A)
102.4 kHz
1/400
2 msec
102.4 kHz
6 (A)
102.4 kHz
1/1000
5 msec
102.4 kHz
7 (A)
102.4 kHz
1/2000
10 msec
102.4 kHz
Configuration
frequency input two
tracks X3/E1, X3/E2
(DFIN1)
10
100 Hz
1/200
1 s
300 Hz
11
1 kHz
1/200
100 msec
3 kHz
12 (A)
10 kHz
1/200
10 msec
10 kHz
13 (A)
10 kHz
1/1000
50 msec
10 kHz
14 (A)
10 kHz
1/10000
500 ms
10 kHz
15 (A)
102.4 kHz
1/400
2 msec
102.4 kHz
16 (A)
102.4 kHz
1/1000
5 msec
102.4 kHz
17 (A)
102.4 kHz
1/2000
10 msec
102.4 kHz
C0426*
Gain frequency
input X3/E1, X3/E2
(A) (DFIN1−GAIN)
100
−1500.0
{0.1 %}
1500.0
C0426
+
f
N
@ p
z
@ C0011 @
100 %
·
f
r
= Normalisation frequency from
C0425
·
p = Number of pole pairs of the motor
·
z = Number of increments per revolution
of the encoder
·
C0011 = Maximum output frequency
(corresponds to maximum process
speed of the motor)
C0427*
Offset frequency
input X3/E1, X3/E2
(A) (DFIN1−OFFSET)
0.0
−100.0
{0.1 %}
100.0