Appendix

Code table

14−49

L

EDB82MV752 EN 5.2

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0430*

v

(A)

Automatic analog
input adjustment

0

0

not active

Gain and offset are calculated by two points
from the setpoint characteristic. Choose
two points distant from each other to
increase the calculation accuracy.
1. Select and input under C0430 which you

want to calculate gain and offset for

2. Enter point 1 under C0431 X value

(setpoint) and Y value (output frequency)

3. Enter point 2 under C0432 X value

(setpoint) and Y value (output frequency)

4. Calculated values are automatically

entered under C0413 (offset) and C0414
(gain)

^ 7−34

1

Input point for X3/1U, X3/1I

2

Input points for X3/2U, X3/2I

C0431*

v

(A)

Coordinates point 1

−100.0

{0.1 %}

100.0

1 X (P1)

−100.0

Analog setpoint of P1
100 % = max. input value (5 V, 10 V or 20 mA)

2 Y (P1)

−100.0

Output frequency of P1
100 % = C0011

C0432*

v

(A)

Coordinates point 2

−100.0

{0.1 %}

100.0

1 X (P2)

100.0

Analog setpoint of P2
100 % = max. input value (5 V, 10 V or 20 mA)

2 Y (P2)

100.0

Output frequency of P2
100 % = C0011

C0435*

v

(A)

Automatic
frequency input
adjustment

0

0
= not active

{1}

4096

·

Only require for speed control with
digital feedback via HTL encoder

·

Calculates the gain C0426, depending
on C0425 and C0011

·

C0426 will be recalculated after every
change of C0011 or C0425.

·

Always enter number of increments
divided by number of pole pairs of
the motor!

– Example: Encoder increments = 4096,

motor 4−pole

Þ C0435 = 2048

C0440
(A)

Additional JOG
values

−650.00

{0.02 Hz}

650.00 JOG = fixed setpoint

Activation via configuration in C0410

^ 7−43

1 JOG 1

20.00

C04401/1 and C0037 are the same

2 JOG 2

30.00

C04401/2 and C0038 are the same

3 JOG 3

40.00

C04401/3 and C0039 are the same

4 JOG 4

15.00

5 JOG 5

25.00

6 JOG 6

35.00

7 JOG 7

45.00

C0469*

s

Function of key

s

of the keypad

1

0

not active

Determines the function which is activated
when pressing

s

.

Changes will only be active after mains
switching!

1

CINH (controller inhibit)

2

QSP (quick stop)

C0500*

Calibration of
numerator variable

2000

1

{1}

25000

·

The codes C0010, C0011, C0017,
C0019, C0037, C0038, C0039, C0044,
C0046, C0049, C0050, C0051, C0138,
C0139, C0140, C0181, C0239, C0625,
C0626, C0627 can be calibrated in a
way that the keypad indicates a process
variable.

·

If C0500/C0501 remain unchanged, the
unit "Hz" will no longer be displayed.

^ 7−86

C0501*

Calibration of
denominator
process variable

10

1

{1}

25000

C0500*
(A)

Calibration of
numerator variable

2000

1

{1}

25000

·

The codes C0037, C0038, C0039,
C0044, C0046, C0049, C0051, C0138,
C0139, C0140, C0181 can be calibrated
in a way that the keypad indicates a
process variable with the unit selected
under C0502.

·

Frequency−related codes (C0010,
C0011, C0017, C0019, C0050, C0239,
C0625, C0626, C0627) are always
indicated in "Hz".

^ 7−86

C0501*
(A)

Calibration of
denominator
process variable

10

1

{1}

25000

C0502*
(A)

Process variable
unit

0

0: Ċ
1: ms
2: s
4: A
5: V

6: rpm
9: °C

10: Hz
11: kVA
12: Nm

13: %
14: kW
15: N
16: mV
17: m

W

18:

W

19: hex
34: m
35: h
42: mH