Appendix, Code table – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 239
Appendix
Code table
14−38
L
EDB82MV752 EN 5.2
Code
IMPORTANT
Possible settings
No.
Selection
Lenze
Name
C0412
v
(cont.)
Analog signal source possible for C0412
^ 7−57
0
Not assigned (FIXED−FREE) or selected via keypad
or parameter channel of an AIF bus module
1
Analog input 1 (AIN1−OUT)
X3/8 (Standard−I/O)
X3/1U or X3/1I (Application−I/O)
2
Frequency input (DFIN1−OUT)
Observe C0410/24, C0425, C0426, C0427
3
Motor potentiometer (MPOT1−OUT)
4 (A)
Analog input 2 (AIN2−OUT)
X3/2U or X3/2I
5 ... 9
Input signal is constantly 0 (FIXED0)
10
AIF input word 1 (AIF−IN.W1)
Only evaluated if C0001 = 3!
11
AIF input word 2 (AIF−IN.W2)
20
CAN−IN1.W1 or FIF−IN.W1
± 24000
º ±480 Hz
2
14
º 100 % rated motor torque
21
CAN−IN1.W2 or FIF−IN.W2
22
CAN−IN1.W3 or FIF−IN.W3
23
CAN−IN1.W4 or FIF−IN.W4
30
CAN−IN2.W1
31
CAN−IN2.W2
32
CAN−IN2.W3
33
CAN−IN2.W4
200
Signals are assigned word by word from fieldbus
function module to FIF (e.g. INTERBUS or
PROFIBUS−DP)
See C0005
228 (A)
PCTRL1−ACT
229 (A)
PCTRL1−SET
230 (A)
PCTRL1−OUT
231 (A)
NSET1−RFG1−IN
232 (A)
NSET1−NOUT
233 (A)
PCTRL1−PID−OUT
234 (A)
PCTRL1−NOUT
255
Not assigned (FIXED−FREE) or selected via keypad
or parameter channel of an AIF bus module
Either NSET1−N1 or NSET1−N2 active
C0413* Offset − analog
inputs
−200.0
{0.1 %}
200.0 The upper limit of the setpoint range from
C0034 corresponds to 100 %
^ 7−34
1 AIN1−OFFSET
0.0
Setting for X3/8 or X3/1U, X3/1I
C0413/1 and C0026 are the same
2 AIN2−OFFSET
0.0
Setting for X3/2U, X3/2I
(only application I/O)
C0414* Gain − analog
inputs
−1500.0
{0.1 %}
1500.0
·
100.0 % = gain 1
·
Inverted setpoint selection through
negative gain and negative offset
1 AIN1−GAIN
100.0
Setting for X3/8 or X3/1U, X3/1I
C0414/1 and C0027 are the same
2 AIN2−GAIN
100.0
Setting for X3/2U, X3/2I
(only application I/O)