beautypg.com

Troubleshooting and fault elimination, Error messages – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual

Page 173

background image

Troubleshooting and fault elimination

Error messages

8−6

L

EDB82MV752 EN 5.2

Remedy

Cause

Fault

PC

1)

Keypad

Pr2

a

73

Faulty PAR2 transfer with
keypad

Parameter set 2 is defective

Pr3

a

77

Faulty PAR3 transfer with
keypad

Parameter set 3 is defective

Pr4

a

78

Faulty PAR4 transfer with
keypad

Parameter set 4 is defective

Pr5

a

79

Internal fault

EEPROM is defective

Contact Lenze

Pt5

a

81

Time error during parameter
set transfer

Data flow from keypad or PC interrupted, e.g.
because keypad was disconnected during transfer

Before enabling the controller, repeat the data transfer or
load the Lenze setting.

rSt

a

76

Error during auto TRIP reset

More than 8 error messages within 10 minutes

Depends on the error message

sd5

a

85

Open circuit − analog input 1

Current at analog input < 4 mA at setpoint range
4 ... 20 mA

Close circuit at analog input

sd7

a

87

Open circuit − analog input 2

1)

LECOM error number, display in Global Drive Control (GDC) parameter setting program