1 v/f characteristic control, V/f characteristic control, Function library – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual

Page 75: Codes for parameter setting

background image

Function library

Selection of control mode, optimisation of operating behaviour

7−4

L

EDB82MV752 EN 5.2

7.1.1

V/f characteristic control

Description

The output voltage of the controller follows a defined characteristic. At low output frequencies, the
characteristic can be boosted. It can be adapted to different load profiles.

·

Linear characteristic for drives with constant load torque over the speed.

·

Quadratic characteristic for drives with quadratic load torque over the speed:

– Quadratic V/f characteristics are preferably used in centrifugal pump and fan drives.

However, it must be checked whether your pump or fan drive can be operated in this
operating mode!

– If your pump or fan drive cannot be used for the operation with a quadratic V/f

characteristic, the linear V/f characteristic or vector control mode must be used.

C0015

V [V]

out

f [Hz]

V

(100 %)

rmot

C0015

V [V]

out

f [Hz]

V

(100 %)

rmot

8200vec540

8200vec539

Fig. 7−2

Linear and square−law V/f characteristic

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze

Selection

C0014

v

Operating mode

2

2

V/f characteristic control V ~ f
(linear characteristic with constant V

min

boost)

·

Commissioning is possible without
identifying motor parameters

·

Advantage of identification with C0148:

– Improved smooth running at low

speeds

– V/f rated frequency (C0015) and slip

(C0021) are calculated and saved.
They must not be entered

^ 7−2

3

V/f characteristic control V ~ f

2

(square−law characteristic with constant V

min

boost)

4

Vector control

In case of the first selection enter the
motor data and identify them with
C0148
Otherwise, commissioning is not
possible
When C0014 = 5, C0019 must be set = 0
(automatic DC injection brake is
deactivated)

5

Sensorless torque control with speed limitation

·

Torque setpoint via C0412/6

·

Speed limitation via setpoint 1 (NSET1−N1) if
C0412/1 is assigned, otherwise via maximum
frequency (C0011)

C0015

uSEr

V/f rated frequency

50.00

7.50

{0.02 Hz}

960.00

·

C0015 is calculated and stored under
C0148 when the motor parameters are
identified

·

Setting applies to all mains voltages
permitted

^ 7−4

^ 7−8

C0016

uSEr

V

min

boost

а

0.00

{0.01 %}

40.00

а

Depending on the controller

Setting applies to all mains voltages
permitted

^ 7−4