Parameter set management

7−93

L

EDB82MV752 EN 5.2

)

Note!

l

Do not remove keypad as long as the parameters are being transmitted! If the
keypad is removed during transmission, the controller indicates the errors "Prx"
or "PT5".

l

A detailed description of the keypads can be found in the "Parameter setting"
chapter.

Restoring the delivery status

1. Attach keypad.

2. Inhibit controller with

s or via terminal (X3/28 = LOW).

3. Set the correct selection number in C0002 from the "Restore delivery status" category and

confirm with

v.

– E.g. C0002 = 1: Parameter set 1 of the controller is overwritten with Lenze setting.

Parameter set transfer from the controller to the keypad

1. Attach keypad.

2. Inhibit controller with

s or via terminal (X3/28 = LOW).

3. Set C0002 = 20 or 50 or 80, confirm with

v.

Parameter set transfer from the keypad to the controller

1. Attach keypad.

2. Inhibit controller with

s or via terminal (X3/28 = LOW).

3. Set the correct selection number In C0002 from the "Parameter set transfer with keypad"

category and confirm with

v.

– E.g. C0002 = 10: All parameter sets of the controller are overwritten with the settings in the

keypad.

– E.g. C0002 = 11: Parameter set 1 of the controller is overwritten with the settings in the

keypad.

Saving your own basic setting

1. Attach keypad.

2. Parameter set 1 must be active!

3. Inhibit controller with

s or via terminal (X3/28 = LOW).

4. Set parameter in parameter set 1.

5. Set C0003 = 3 and confirm with

v.

6. Set C0002 = 9 and confirm with

v. The own basic setting is saved.

7. Set C0003 = 1 and confirm with

v.

Copying your own basic setting into the parameter sets

1. Attach keypad.

2. Inhibit controller with

s or via terminal (X3/28 = LOW).

3. Set the correct selection number in C0002 from the "Loading/saving you own basic setting"

category and confirm with

v.

– E.g. C0002 = 5: Parameter set 1 is overwritten with your own basic setting.

– E.g. C0002 = 8: Parameter set 4 is overwritten with your own basic setting.