Process controller, current limitation controller

7−51

L

EDB82MV752 EN 5.2

Pressure control and flow control

·

The differential component K

D

(C0072) is generally not required for pressure and flow control.

·

Set the influence (C0074) to 100 %.

·

Deactivate the frequency feedforward control (C0238 = 0).

Code

Setting for

Gases

Fluids

C0070 (K

P

)

0.1

0.02 ... 0.1

C0071 (T

N

)

5000 (T

N

= 5 s)

200 ... 1000 (T

N

= 0.2 s ... 1 s)

C0072 (K

D

)

0

0

Speed control

Code

Setting

C0070 (K

P

)

5

C0071 (T

N

)

100 (T

N

= 0.1 s)

C0072 (K

D

)

0

Setting of process controller influence

·

Activate frequency feedforward control (C0238 = 1). Now the process controller has only
limited influence:

– The control factor determines the influence of the process controller (C0074).

– Control factor = C0050 (output frequency) − C0051 (actual process controller value)

·

C0074 refers to the maximum output frequency C0011.

·

C0074 influences the stability of the control loop:

– Set C0074 as low as possible.

– If C0074 is set too high, the control loop can become unstable.

Calculation of process controller influence

Calculate C0074

Example

C0074 [%]

+ C0050 * C0051

C0011

@ 100 %

C0011 = 50 Hz, C0050 = 53 Hz, C0051 = 50 Hz:

C0074 [%]

+ 53 Hz * 50 Hz

50 Hz

@ 100 % + 6 %

Set the influence so that the process controller output covers the calculated value in every working
point.

Set C0074 = 10 % as guide value for the example (C0074 = 6 %). The guide value contains
tolerances which must always be observed.

Example of additive influence

The effective direction of the process controller output to the main setpoint is additive.

Settings

·

C0051 = positive actual value

·

C0181 = select positive setpoint

·

C0238 = 1 (with frequency feedforward control)

·

Potentiometer terminals of the dancer

– End (E) = +10 V

– Start (A) = GND