2 diagnostics, Diagnostics, Function library – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 160: Display of operating data, diagnostics
Function library
Display of operating data, diagnostics
7−89
L
EDB82MV752 EN 5.2
7.14.2
Diagnostics
Description
Display codes for diagnostics
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0093*
Controller type
xxxy
Only display
·
xxx = Power taken from nameplate (e.
g. 551 = 550 W)
·
y = Voltage class (2 = 240 V, 4 = 400 V)
C0099*
Software version
x.y
Only display
x = Main version, y = Index
C0161*
Active error
Display history buffer contents
·
Keypad: three−digit, alpha numerical
fault detection
·
9371BB keypad: LECOM fault number
^ 8−1
C0162*
Last fault
C0163*
Last but one fault
C0164*
Last but two fault
C0168*
Actual fault
History buffer displays "active error"
·
Keypad: three−digit, alpha numerical
fault detection
·
9371BB keypad: LECOM fault number
^ 8−1
C0179*
Power−on time
{h}
Only display
Total time mains on
C0183*
Diagnostics
0
No fault
Only display
102
TRIP active
104
Message "Overvoltage (
OU
)" or "Undervoltage
(
LU
)" active
142
Pulse inhibit
151
Quick stop active
161
DC−injection brake active
250
Warning active
C0200*
Software ID
Read only on PC
x = main version, y = subversion
82S8212V_xy000
8200 vector 0.25 ... 11 kW
82S8212V_xy010
8200 vector 15 ... 90 kW
C0201*
Software creation
date
Read only on PC
C0202*
Software ID
Output in keypad as string in four parts at four characters
each
Read only in keypad
1
82S8
2
212 V
3
_xy0
x = main version, y = subversion
4
zz
00 = 8200 vector 0.25 ... 11 kW
10 = 8200 vector 15 ... 90 kW
C0304
Service codes
Modifications only by Lenze Service!
...
C0309
C0372*
Function module
identification
0
No function module
Only display
1
Standard I/O or AS−i
2
System bus (CAN)
6
Other function module on FIF
e.g. application I/O, INTERBUS, ...
10
No valid recognition
C0518 Service codes
Modifications only by Lenze Service!
C0519