Function library
Free connection of digital signals, message output
7−73
L
EDB82MV752 EN 5.2
7.11.2
Free configuration of digital outputs
Description
·
The digital outputs (X3/A1, X3/A2, relay output K1
1
or digital switching output K1
2
) can be
linked freely with internal digital signals.
·
A signal source can be linked with several targets.
)
Hinweis!
l
C0008 enables the relay output K1
1
or the digital switching output K1
2
to be also
linked permanently with some internal signal sources. C0415/1 is then adapted
automatically.
l
C0117 enables the digital output X3/A1 to be also linked permanently with some
internal signal sources. C0415/2 is then adapted automatically.
1) for device version 151
2) for device versions 152 and 153
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0415
v
Free configuration
of digital outputs
Output of digital signals to terminals
For configuration of relay output K2 see
C0409
^ 7−73
1 Relay output K1
(RELAY, motec
version 151)
Digital switching
output K1 (motec
version 152, 153)
25
TRIP error message (DCTRL1−TRIP)
A selection in C0008 is copied into
C0415/1. Change of C0415/1 sets
C0008 = 255!
2 Digital output X3/A1
(DIGOUT1)
16
Ready for operation (DCTRL1−RDY)
A selection in C0117 is copied into
C0415/2. Change of C0415/2 sets
C0117 = 255!
3 (A) Digital output X3/A2
(DIGOUT2)
255
Not assigned (FIXED−FREE)