Page 187: Execute motor parameter identification

background image

Application examples

Pressure control

13−2

L

EDB82MV752 EN 5.2

Application−specific configuration

·

Execute motor parameter identification.

(

^ 7−48)

Code

Settings

Important

No.

Name

Value

Meaning

C0014

↵ Operating mode

3

V/f characteristic control V ~ f

square−law characteristic with constant V

min

boost

C0410

Digital signal source

8 DOWN

1

E1

Inputs of the UP" and DOWN" pushbuttons

7 UP

2

E2

1 JOG1/3

3

E3

Fixed speed for night−time pressure reduction

Applying the fixed speed simultaneously

deactivates the process controller.

19 PCTRL1−OFF

3

E3

Deactivation of process controller

17 H/Re

4

E4

Changeover − PLC/on−site set−up

C0412

Analog signal source

1 Setpoint 1

(NSET1-N1)

4

X3/2I

Pressure setpoint (manual)

2 Setpoint 2

(NSET1-N2)

3

MPOT1−OUT motor potentiometer function

Pressure setpoint (remote)

5 Actual process

controller value
(PCTRL1−ACT)

1

X3/1U

Actual pressure value

C0145 Source − process

controller setpoint

0

Overall setpoint (PCTRL1−SET3)

Main setpoint + additional setpoint

C0070 Process controller

gain

à

Adapt to process, if required.

à

Further information:

^ 7−50 ff.

C0071 Process controller

reset time

à

C0072 Differential

component of
process controller

à

C0074 Process controller

influence

100.0

0.0

{0.1 %}

100.0

C0238

↵ Frequency precontrol

−0−

−0−

No feedforward control (only process controller)

Process controller has full influence.

C0419 Free configuration of

analog outputs

Analog signal source

1 X3/62 (AOUT1−IN)

8

Actual process controller value

C0037 JOG1

17

Fixed reduction to approx. 1/3 of the rated
motor speed.

C0239o Lower frequency

limitation

10.00

Setpoint−independent minimum speed.

C0182* Integration time

S ramps

0.50 s

Jerk−free starting action

C0625* Blocking frequency 1

30.00 Hz

C0628* Skipping bandwidth −

skip frequency

10.00 %

with regard to C0625

C0119

↵ Configuration of PTC

input/earth−fault
detection

4

PTC input is active, TRIP is effected

C0415 Free configuration of

digital outputs

1 Relay output K1

1

or
digital switching
output K1

2

16

Ready for operation

1: applies to motec version 151

2: applies to motec version 152, 153

2 Digital output X3/A1

25

TRIP error message