Application examples, Pressure control, Application−specific configuration – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 187: Execute motor parameter identification
Application examples
Pressure control
13−2
L
EDB82MV752 EN 5.2
Application−specific configuration
·
Execute motor parameter identification.
(
^ 7−48)
Code
Settings
Important
No.
Name
Value
Meaning
C0014
↵ Operating mode
3
V/f characteristic control V ~ f
square−law characteristic with constant V
min
boost
C0410
Digital signal source
8 DOWN
1
E1
Inputs of the UP" and DOWN" pushbuttons
7 UP
2
E2
1 JOG1/3
3
E3
Fixed speed for night−time pressure reduction
Applying the fixed speed simultaneously
deactivates the process controller.
19 PCTRL1−OFF
3
E3
Deactivation of process controller
17 H/Re
4
E4
Changeover − PLC/on−site set−up
C0412
Analog signal source
1 Setpoint 1
(NSET1-N1)
4
X3/2I
Pressure setpoint (manual)
2 Setpoint 2
(NSET1-N2)
3
MPOT1−OUT motor potentiometer function
Pressure setpoint (remote)
5 Actual process
controller value
(PCTRL1−ACT)
1
X3/1U
Actual pressure value
C0145 Source − process
controller setpoint
0
Overall setpoint (PCTRL1−SET3)
Main setpoint + additional setpoint
C0070 Process controller
gain
à
Adapt to process, if required.
à
Further information:
^ 7−50 ff.
C0071 Process controller
reset time
à
C0072 Differential
component of
process controller
à
C0074 Process controller
influence
100.0
0.0
{0.1 %}
100.0
C0238
↵ Frequency precontrol
−0−
−0−
No feedforward control (only process controller)
Process controller has full influence.
C0419 Free configuration of
analog outputs
Analog signal source
1 X3/62 (AOUT1−IN)
8
Actual process controller value
C0037 JOG1
17
Fixed reduction to approx. 1/3 of the rated
motor speed.
C0239o Lower frequency
limitation
10.00
Setpoint−independent minimum speed.
C0182* Integration time
S ramps
0.50 s
Jerk−free starting action
C0625* Blocking frequency 1
30.00 Hz
C0628* Skipping bandwidth −
skip frequency
10.00 %
with regard to C0625
C0119
↵ Configuration of PTC
input/earth−fault
detection
4
PTC input is active, TRIP is effected
C0415 Free configuration of
digital outputs
1 Relay output K1
1
or
digital switching
output K1
2
16
Ready for operation
1: applies to motec version 151
2: applies to motec version 152, 153
2 Digital output X3/A1
25
TRIP error message