Appendix

Code table

14−12

L

EDB82MV752 EN 5.2

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0002*

s
uSEr

(cont.)

Saving of own
settings

9

PAR1

ð Own settings

You can save your own basic settings for a
controller (e.g. machine delivery status):
1. Ensure that parameter set 1 is active
2. Controller inhibit
3. Set C0003 = 3, acknowledge with

v

4. Set C0002 = 9, acknowledge with

v

,

to save your own basic settings

5. Set C0003 = 1, acknowledge with

v

6. Enable the controller.

C0002*

s
uSEr

(cont.)

Loading/copying of
your own basic
settings

Using this function, PAR1 can be copied to
parameter sets PAR2 ... PAR4

5

Own settings

ð PAR1

Restorage of own basic setting in the
selected parameter set

6

Own settings

ð PAR2

7

Own settings

ð PAR3

8

Own settings

ð PAR4

C0003*

v

Non−volatile
parameter saving

1

0

Parameter not saved in EEPROM

Data loss after mains disconnection

1

Parameter always saved in EEPROM

·

Active after every mains connection

·

Cyclic parameter changes via bus
module are not allowed.

3

Own settings saved in EEPROM

Subsequently save parameter set 1 as own
basic setting with C0002 = 9

C0004*

Bar−graph display

56

1

{Code No.}

989

·

Bargraph display indicates the selected
value in % after power on

·

Range −180 % ... +180 %

56 = controller load (C0056)

C0005

V

Fixed configuration
of analog input
signals

0

Change of C0005 is copied into the
corresponding subcode of C0412. Free
configuration in C0412 sets
C0005 = 255!
Observe the following in case of
configurations with frequency input:

·

Activate the frequency input X3/E1,
X3/E2 with C0410/24 = 1.

·

Delete all existing signal connections of
the digital inputs in C0410 used by the
frequency input.

·

Configure frequency input with C0425
and C0426

^ 7−57

0

Setpoint for speed control via X3/8 or X3/1U,
X3/1I

1

Setpoint for speed control via X3/8 with setpoint
summation via frequency input

2

Setpoint for speed control via frequency input
with setpoint summation via X3/8

3

Setpoint for speed control via frequency input,
torque limitation via X3/8 (power control)

4

Setpoint for sensorless torque control via X3/8,
speed limitation via C0011

Only active if C0014 = −5− (torque
selection)

5

Setpoint for sensorless torque control via X3/8,
speed limitation via frequency input

6

Controlled operation; setpoint via X3/8 with digital
feedback via frequency input

7

Controlled operation, setpoint via frequency input
X3/E1 with analog feedback via X3/8

200

All digital and analog input signals are from the
fieldbus function module on FIF (e.g. INTERBUS,
PROFIBUS−DP, CANopen or DeviceNet)

Sets C0410/x = 200 and C0412/x = 200

255

Free configuration in C0412

Read only
Do not change C0005 since settings in
C0412 may get lost