Appendix, Code table – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 213
Appendix
Code table
14−12
L
EDB82MV752 EN 5.2
Code
IMPORTANT
Possible settings
No.
Selection
Lenze
Name
C0002*
s
uSEr
(cont.)
Saving of own
settings
9
PAR1
ð Own settings
You can save your own basic settings for a
controller (e.g. machine delivery status):
1. Ensure that parameter set 1 is active
2. Controller inhibit
3. Set C0003 = 3, acknowledge with
v
4. Set C0002 = 9, acknowledge with
v
,
to save your own basic settings
5. Set C0003 = 1, acknowledge with
v
6. Enable the controller.
C0002*
s
uSEr
(cont.)
Loading/copying of
your own basic
settings
Using this function, PAR1 can be copied to
parameter sets PAR2 ... PAR4
5
Own settings
ð PAR1
Restorage of own basic setting in the
selected parameter set
6
Own settings
ð PAR2
7
Own settings
ð PAR3
8
Own settings
ð PAR4
C0003*
v
Non−volatile
parameter saving
1
0
Parameter not saved in EEPROM
Data loss after mains disconnection
1
Parameter always saved in EEPROM
·
Active after every mains connection
·
Cyclic parameter changes via bus
module are not allowed.
3
Own settings saved in EEPROM
Subsequently save parameter set 1 as own
basic setting with C0002 = 9
C0004*
Bar−graph display
56
1
{Code No.}
989
·
Bargraph display indicates the selected
value in % after power on
·
Range −180 % ... +180 %
56 = controller load (C0056)
C0005
V
Fixed configuration
of analog input
signals
0
Change of C0005 is copied into the
corresponding subcode of C0412. Free
configuration in C0412 sets
C0005 = 255!
Observe the following in case of
configurations with frequency input:
·
Activate the frequency input X3/E1,
X3/E2 with C0410/24 = 1.
·
Delete all existing signal connections of
the digital inputs in C0410 used by the
frequency input.
·
Configure frequency input with C0425
and C0426
^ 7−57
0
Setpoint for speed control via X3/8 or X3/1U,
X3/1I
1
Setpoint for speed control via X3/8 with setpoint
summation via frequency input
2
Setpoint for speed control via frequency input
with setpoint summation via X3/8
3
Setpoint for speed control via frequency input,
torque limitation via X3/8 (power control)
4
Setpoint for sensorless torque control via X3/8,
speed limitation via C0011
Only active if C0014 = −5− (torque
selection)
5
Setpoint for sensorless torque control via X3/8,
speed limitation via frequency input
6
Controlled operation; setpoint via X3/8 with digital
feedback via frequency input
7
Controlled operation, setpoint via frequency input
X3/E1 with analog feedback via X3/8
200
All digital and analog input signals are from the
fieldbus function module on FIF (e.g. INTERBUS,
PROFIBUS−DP, CANopen or DeviceNet)
Sets C0410/x = 200 and C0412/x = 200
255
Free configuration in C0412
Read only
Do not change C0005 since settings in
C0412 may get lost