Function library, Parameter set management – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual

Page 163

background image

Function library

Parameter set management

7−92

L

EDB82MV752 EN 5.2

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0002*

s
uSEr

(cont.)

Parameter set
transfer using the
keypad

Keypad

ð PAR1 (+ FPAR1)

Overwrite selected parameter set and, if
necessary, FPAR1 with the corresponding
keypad data

71

With function module Application−I/O, INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen

11

With all other function modules

Keypad

ð PAR2 (+ FPAR1)

72

With function module Application−I/O, INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen

12

With all other function modules

Keypad

ð PAR3 (+ FPAR1)

73

With function module Application−I/O, INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen

13

With all other function modules

Keypad

ð PAR4 (+ FPAR1)

74

With function module Application−I/O, INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen

14

With all other function modules

Controller

ð Keypad

All available parameter sets (PAR1 ... PAR4,
and FPAR1) are copied to the keypad

80

With function module Application−I/O, INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen

20

With all other function modules

Keypad

ð Function module

Overwrite the module−specific parameter
set FPAR1 only

40

Only with function module INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen

Function module

ð Keypad

Copy the module−specific parameter set
FPAR1 only

50

Only with function module INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen

C0002*

s
uSEr

(cont.)

Saving of own
settings

9

PAR1

ð Own settings

You can save your own basic settings for a
controller (e.g. machine delivery status):
1. Ensure that parameter set 1 is active
2. Controller inhibit
3. Set C0003 = 3, acknowledge with

v

4. Set C0002 = 9, acknowledge with

v

,

to save your own basic settings

5. Set C0003 = 1, acknowledge with

v

6. Enable the controller.

C0002*

s
uSEr

(cont.)

Loading/copying of
your own basic
settings

Using this function, PAR1 can be copied to
parameter sets PAR2 ... PAR4

5

Own settings

ð PAR1

Restorage of own basic setting in the
selected parameter set

6

Own settings

ð PAR2

7

Own settings

ð PAR3

8

Own settings

ð PAR4

C0003*

v

Non−volatile
parameter saving

1

0

Parameter not saved in EEPROM

Data loss after mains disconnection

1

Parameter always saved in EEPROM

·

Active after every mains connection

·

Cyclic parameter changes via bus
module are not allowed.

3

Own settings saved in EEPROM

Subsequently save parameter set 1 as own
basic setting with C0002 = 9