Function library, Parameter set management – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 163
![background image](/manuals/566255/163/background.png)
Function library
Parameter set management
7−92
L
EDB82MV752 EN 5.2
Code
IMPORTANT
Possible settings
No.
Selection
Lenze
Name
C0002*
s
uSEr
(cont.)
Parameter set
transfer using the
keypad
Keypad
ð PAR1 (+ FPAR1)
Overwrite selected parameter set and, if
necessary, FPAR1 with the corresponding
keypad data
71
With function module Application−I/O, INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen
11
With all other function modules
Keypad
ð PAR2 (+ FPAR1)
72
With function module Application−I/O, INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen
12
With all other function modules
Keypad
ð PAR3 (+ FPAR1)
73
With function module Application−I/O, INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen
13
With all other function modules
Keypad
ð PAR4 (+ FPAR1)
74
With function module Application−I/O, INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen
14
With all other function modules
Controller
ð Keypad
All available parameter sets (PAR1 ... PAR4,
and FPAR1) are copied to the keypad
80
With function module Application−I/O, INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen
20
With all other function modules
Keypad
ð Function module
Overwrite the module−specific parameter
set FPAR1 only
40
Only with function module INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen
Function module
ð Keypad
Copy the module−specific parameter set
FPAR1 only
50
Only with function module INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen
C0002*
s
uSEr
(cont.)
Saving of own
settings
9
PAR1
ð Own settings
You can save your own basic settings for a
controller (e.g. machine delivery status):
1. Ensure that parameter set 1 is active
2. Controller inhibit
3. Set C0003 = 3, acknowledge with
v
4. Set C0002 = 9, acknowledge with
v
,
to save your own basic settings
5. Set C0003 = 1, acknowledge with
v
6. Enable the controller.
C0002*
s
uSEr
(cont.)
Loading/copying of
your own basic
settings
Using this function, PAR1 can be copied to
parameter sets PAR2 ... PAR4
5
Own settings
ð PAR1
Restorage of own basic setting in the
selected parameter set
6
Own settings
ð PAR2
7
Own settings
ð PAR3
8
Own settings
ð PAR4
C0003*
v
Non−volatile
parameter saving
1
0
Parameter not saved in EEPROM
Data loss after mains disconnection
1
Parameter always saved in EEPROM
·
Active after every mains connection
·
Cyclic parameter changes via bus
module are not allowed.
3
Own settings saved in EEPROM
Subsequently save parameter set 1 as own
basic setting with C0002 = 9