Commissioning

Vector control

5−12

L

EDB82MV752 EN 5.2

5.5.2

Commissioning with standard I/O function module

The following instructions apply to controllers equipped with a standard−I/O function module and a
three−phase AC motor which has been selected according to a power−based assignment.

1.

Connect the keypad

2.

Ensure that controller inhibit is active after mains connection

misc001

20

28

X3

}

Terminal X3/28 = LOW

3.

Switch on the mains

ON

misc002

4.

The keypad is in "Disp" mode after approx. 2 s and indicates
the output frequency (C0050)

000

000

a

b

c

d

e

‚

m n o

p

q r

Hi

Hz

Lo

1

j g f k i h PS

Œ

0050

The

USEr

menu is active

5.

Go to the

ALL

menu

6.

Change to the

f

mode to configure the basic settings for

your drive

000

000

a

b

c

d

e

‚m n o

p

q r

Hi

Hz

Lo

1

j g f k i h PS

Œ

0050

z
y

w x

Blinking on the display:

0050

7.

Adapt the terminal configuration to the wiring (C0007)
Lenze setting: −0−, i. e.
E1: JOG1/3 fixed setpoint selection
E2: JOG2/3
E3: DCB DC injection brake
E4: CW/CCW rotation

z
y

w x

0

000

a

b

c

d

e

‚m n o

p

q r

Hi
Lo

1

j g f k i h PS

Œ

0007

8.

Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz

0 %

[f]

100 %

C0011

C0010

9.

Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz

10.

Set the acceleration time T

ir

(C0012)

Lenze setting: 5.00 s

f [ H z ]

f 2

C 0 0 1 1

f 1

0

t i r

t i f

T i r

T i f

t

T

ir

+ t

ir

@

C0011

f

2 *

f

1

t

ir

= acceleration time wanted

11.

Set the deceleration time T

if

(C0013)

Lenze setting: 5.00 s

T

if

+ t

if

@

C0011

f

2 *

f

1

t

if

= deceleration time wanted

12.

Activate the control mode "vector control" (C0014 = 4)
Lenze setting: Linear V/f characteristic control (C0014 = 2)

E82ZBC014

z
y

w x

v

t

u

s

4

00 14

000

1

c

d

f

PS

Œ

p

Para

H/L

Subcode

Disp

Set

13.

Adapt the voltage/current range for the analog setpoint
selection (C0034)
Lenze setting: −0−, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)

z
y

w x

0

000

a

b

c

d

e

‚m n o

p

q r

Hi
Lo

1

j g f k i h PS

Œ

0034

Set the DIP switch on the standard I/O to the
same range (see Mounting Instructions for the
standard I/O)

14.

Enter the motor data

See motor nameplate

A

Rated motor speed (C0087)
Lenze setting: 1390 rpm

B

Rated motor current (C0088)
Lenze setting: Depends on the controller

Enter the value for the motor connection type
(star/delta) selected!

C

Rated motor frequency (C0089)
Lenze setting: 50 Hz

D

Rated motor voltage (C0090)
Lenze setting: Depends on the controller

Enter the value for the motor connection type
(star/delta) selected!

E

Motor−cos

j (C0091)

Lenze setting: Depends on the controller