Commissioning
Vector control
5−12
L
EDB82MV752 EN 5.2
5.5.2
Commissioning with standard I/O function module
The following instructions apply to controllers equipped with a standard−I/O function module and a
three−phase AC motor which has been selected according to a power−based assignment.
1.
Connect the keypad
2.
Ensure that controller inhibit is active after mains connection
misc001
20
28
X3
}
Terminal X3/28 = LOW
3.
Switch on the mains
ON
misc002
4.
The keypad is in "Disp" mode after approx. 2 s and indicates
the output frequency (C0050)
000
000
a
b
c
d
e
m n o
p
q r
Hi
Hz
Lo
1
j g f k i h PS
0050
The
USEr
menu is active
5.
Go to the
ALL
menu
6.
Change to the
f
mode to configure the basic settings for
your drive
000
000
a
b
c
d
e
m n o
p
q r
Hi
Hz
Lo
1
j g f k i h PS
0050
z
y
w x
Blinking on the display:
0050
7.
Adapt the terminal configuration to the wiring (C0007)
Lenze setting: −0−, i. e.
E1: JOG1/3 fixed setpoint selection
E2: JOG2/3
E3: DCB DC injection brake
E4: CW/CCW rotation
z
y
w x
0
000
a
b
c
d
e
m n o
p
q r
Hi
Lo
1
j g f k i h PS
0007
8.
Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz
0 %
[f]
100 %
C0011
C0010
9.
Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz
10.
Set the acceleration time T
ir
(C0012)
Lenze setting: 5.00 s
f [ H z ]
f 2
C 0 0 1 1
f 1
0
t i r
t i f
T i r
T i f
t
T
ir
+ t
ir
@
C0011
f
2 *
f
1
t
ir
= acceleration time wanted
11.
Set the deceleration time T
if
(C0013)
Lenze setting: 5.00 s
T
if
+ t
if
@
C0011
f
2 *
f
1
t
if
= deceleration time wanted
12.
Activate the control mode "vector control" (C0014 = 4)
Lenze setting: Linear V/f characteristic control (C0014 = 2)
E82ZBC014
z
y
w x
v
t
u
s
4
00 14
000
1
c
d
f
PS
p
Para
H/L
Subcode
Disp
Set
13.
Adapt the voltage/current range for the analog setpoint
selection (C0034)
Lenze setting: −0−, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)
z
y
w x
0
000
a
b
c
d
e
m n o
p
q r
Hi
Lo
1
j g f k i h PS
0034
Set the DIP switch on the standard I/O to the
same range (see Mounting Instructions for the
standard I/O)
14.
Enter the motor data
See motor nameplate
A
Rated motor speed (C0087)
Lenze setting: 1390 rpm
B
Rated motor current (C0088)
Lenze setting: Depends on the controller
Enter the value for the motor connection type
(star/delta) selected!
C
Rated motor frequency (C0089)
Lenze setting: 50 Hz
D
Rated motor voltage (C0090)
Lenze setting: Depends on the controller
Enter the value for the motor connection type
(star/delta) selected!
E
Motor−cos
j (C0091)
Lenze setting: Depends on the controller