Appendix

Code table

14−50

L

EDB82MV752 EN 5.2

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0517*

v

User menu

·

After mains switching or when using the
function

g

the code from C0517/1

will be displayed.

·

In Lenze setting, the user menu contains
the most important codes for starting−up
the control mode "V/f characteristic
control with linear characteristic"

·

When the password protection is
activated, only the codes entered under
C0517 are freely accessible.

·

Enter the required code numbers in the
subcodes.

Codes, which are only active when
being used together with an
Application−I/O, cannot be entered!

^ 7−95

1 Memory 1

50

C0050

Output frequency (MCTRL1−NOUT)

2 Memory 2

34

C0034

Analog setpoint selection range

3 Memory 3

7

C0007

Fixed configuration − digital input signals

4 Memory 4

10

C0010

Minimum output frequency

5 Memory 5

11

C0011

Maximum output frequency

6 Memory 6

12

C0012

Acceleration time main setpoint

7 Memory 7

13

C0013

Deceleration time main setpoint

8 Memory 8

15

C0015

V/f rated frequency

9 Memory 9

16

C0016

U

min

boost

10 Memory 10

2

C0002

Parameter set transfer

C0518 Service codes

Modifications only by Lenze Service!

C0519

C0520

C0597*

v

Configuration of
motor phase failure
detection −28−

0

0

not active

1

TRIP fault message

Keypad:

LP1

, bus: 32

2

Warning

Keypad:

LP1

, bus: 182

C0599*

v

Current limit value
for motor phase
failure detection

5

1

{1 %}

50

·

Threshold for C0597

·

Reference: Rated controller current

C0608*

Fan monitoring

0

0

Not active

8200 motec 3 ... 7.5 kW:
Function must be activated during
commissioning (recommended: C0608 = 1)!
Otherwise, the controller may be destroyed
through overheating.
For all other controllers:
It is essential to set C0608 = 0.

1

TRIP error message

2

Warning

C0625*

Skip frequency 1

0.00

0.00

{0.02 Hz}

650.00

^ 7−17

C0626*

Skip frequency 2

0.00

0.00

{0.02 Hz}

650.00

C0627*

Skip frequency 3

0.00

0.00

{0.02 Hz}

650.00

C0628*

Bandwidth of skip
frequencies

0.00

0.00

{0.01 %}

100.00 Applies to C0625, C0626, C0627

C0988*

DC−bus voltage
threshold for
DC−bus voltage
control

0

0
Parameter set
changeover via
DC−bus voltage
deactivated

{1 %}

200

·

Changeover always between PAR1 nd
PAR2

·

Parameter set changeover is not
possible via terminal, bus or PC if
C988 > 0!

C1500*
(A)

Software number
application I/O

82SAFA0B_xy000

Only PC display
x = main version
y = subversion

C1501*
(A)

Software creation
date application I/O

Only PC display

C1502*
(A)

Software ID
application I/O

Output in keypad as string in four parts at four characters
each

Read only in keypad
x = main version
y = subversion

1

82SA

2

FA0B

3

_xy0

4

00

C1504
(A)

Service codes
application I/O

Modifications only by Lenze Service!

...

C1507
(A)

C1550
(A)

Service code
application I/O

Modifications only by Lenze Service!