14−50, c0597), Appendix, Code table – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 251
![background image](/manuals/566255/251/background.png)
Appendix
Code table
14−50
L
EDB82MV752 EN 5.2
Code
IMPORTANT
Possible settings
No.
Selection
Lenze
Name
C0517*
v
User menu
·
After mains switching or when using the
function
g
the code from C0517/1
will be displayed.
·
In Lenze setting, the user menu contains
the most important codes for starting−up
the control mode "V/f characteristic
control with linear characteristic"
·
When the password protection is
activated, only the codes entered under
C0517 are freely accessible.
·
Enter the required code numbers in the
subcodes.
Codes, which are only active when
being used together with an
Application−I/O, cannot be entered!
^ 7−95
1 Memory 1
50
C0050
Output frequency (MCTRL1−NOUT)
2 Memory 2
34
C0034
Analog setpoint selection range
3 Memory 3
7
C0007
Fixed configuration − digital input signals
4 Memory 4
10
C0010
Minimum output frequency
5 Memory 5
11
C0011
Maximum output frequency
6 Memory 6
12
C0012
Acceleration time main setpoint
7 Memory 7
13
C0013
Deceleration time main setpoint
8 Memory 8
15
C0015
V/f rated frequency
9 Memory 9
16
C0016
U
min
boost
10 Memory 10
2
C0002
Parameter set transfer
C0518 Service codes
Modifications only by Lenze Service!
C0519
C0520
C0597*
v
Configuration of
motor phase failure
detection −28−
0
0
not active
1
TRIP fault message
Keypad:
LP1
, bus: 32
2
Warning
Keypad:
LP1
, bus: 182
C0599*
v
Current limit value
for motor phase
failure detection
5
1
{1 %}
50
·
Threshold for C0597
·
Reference: Rated controller current
C0608*
Fan monitoring
0
0
Not active
8200 motec 3 ... 7.5 kW:
Function must be activated during
commissioning (recommended: C0608 = 1)!
Otherwise, the controller may be destroyed
through overheating.
For all other controllers:
It is essential to set C0608 = 0.
1
TRIP error message
2
Warning
C0625*
Skip frequency 1
0.00
0.00
{0.02 Hz}
650.00
^ 7−17
C0626*
Skip frequency 2
0.00
0.00
{0.02 Hz}
650.00
C0627*
Skip frequency 3
0.00
0.00
{0.02 Hz}
650.00
C0628*
Bandwidth of skip
frequencies
0.00
0.00
{0.01 %}
100.00 Applies to C0625, C0626, C0627
C0988*
DC−bus voltage
threshold for
DC−bus voltage
control
0
0
Parameter set
changeover via
DC−bus voltage
deactivated
{1 %}
200
·
Changeover always between PAR1 nd
PAR2
·
Parameter set changeover is not
possible via terminal, bus or PC if
C988 > 0!
C1500*
(A)
Software number
application I/O
82SAFA0B_xy000
Only PC display
x = main version
y = subversion
C1501*
(A)
Software creation
date application I/O
Only PC display
C1502*
(A)
Software ID
application I/O
Output in keypad as string in four parts at four characters
each
Read only in keypad
x = main version
y = subversion
1
82SA
2
FA0B
3
_xy0
4
00
C1504
(A)
Service codes
application I/O
Modifications only by Lenze Service!
...
C1507
(A)
C1550
(A)
Service code
application I/O
Modifications only by Lenze Service!