Appendix, Code table – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 240
Appendix
Code table
14−39
L
EDB82MV752 EN 5.2
Code
IMPORTANT
Possible settings
No.
Selection
Lenze
Name
C0415
v
Free configuration
of digital outputs
Output of digital signals to terminals
For configuration of relay output K2 see
C0409
^ 7−73
1 Relay output K1
(RELAY, motec
version 151)
Digital switching
output K1 (motec
version 152, 153)
25
TRIP error message (DCTRL1−TRIP)
A selection in C0008 is copied into
C0415/1. Change of C0415/1 sets
C0008 = 255!
2 Digital output X3/A1
(DIGOUT1)
16
Ready for operation (DCTRL1−RDY)
A selection in C0117 is copied into
C0415/2. Change of C0415/2 sets
C0117 = 255!
3 (A) Digital output X3/A2
(DIGOUT2)
255
Not assigned (FIXED−FREE)
C0415
v
(cont.)
Possible digital signals for C0415
^ 7−73
0
Not assigned (FIXED−FREE)
1
Parameter set 2 or parameter set 4 is active
(DCTRL1−PAR−B0)
PAR−B1
PAR−B0
LOW
LOW
LOW
HIGH
HIGH
LOW
HIGH
HIGH
Active
PAR1
PAR2
PAR3
PAR4
2
Pulse inhibit active (DCTRL1−IMP)
3
I
max
limit reached (MCTRL1−IMAX)
(C0014 = −5−: torque setpoint reached)
4
Frequency setpoint reached
(DCTRL1−RFG1=NOUT)
5
Ramp function generator 1: input = output
(NSET1−RFG1−I=O)
RFG1 = ramp function generator − main
setpoint
6
Values have fallen below frequency threshold
Q
min
(f < C0017) (PCTRL1−QMIN)
LOW active
7
Output frequency = 0 (DCTRL1−NOUT=0)
8
Controller inhibit active (DCTRL1−CINH)
9 ... 12
Reserved
13
Group signal (DCTRL1−OH−PTC−LP1−FAN1−WARN):
Overtemperature warning (
J
max
− 5 °C)
(DCTRL1−OH−WARN)
or
Motor overtemperature warning
or
Set C0119 = 2 or C0119 = 5
Motor phase failure warning (DCTRL1−LP1−WARN)
or
Set C0597 = 2
Fan failure warning (DCTRL1−FAN1−WARN)
(only active with 8200 motec and C0608 = 1))
With 8200 vector, C0608 must be set to 0
14
DC bus overvoltage (DCTRL1−OV)
15
CCW rotation (DCTRL1−CCW)
16
Ready for operation (DCTRL1−RDY)
17
Parameter set 3 or parameter set 4 active
(DCTRL1−PAR−B1)
PAR−B1
PAR−B0
LOW
LOW
LOW
HIGH
HIGH
LOW
HIGH
HIGH
Active
PAR1
PAR2
PAR3
PAR4
18
Values have fallen below TRIP or Q
min
or pulse
inhibit (IMP) is active (DCTRL1−TRIP−QMIN−IMP)
LOW active
19
PTC warning (DCTRL1−PTC−WARN)
Set C0119 = 2 or C0119 = 5
Status of relay K
SR
Only with 8200 vector 15 ...90 kW, variant
"safe standstill":
HIGH = pulse inhibit active by "safe
standstill"
LOW = no pulse inhibit by "safe standstill"