Appendix

Code table

14−39

L

EDB82MV752 EN 5.2

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0415

v

Free configuration
of digital outputs

Output of digital signals to terminals

For configuration of relay output K2 see
C0409

^ 7−73

1 Relay output K1

(RELAY, motec
version 151)
Digital switching
output K1 (motec
version 152, 153)

25

TRIP error message (DCTRL1−TRIP)

A selection in C0008 is copied into
C0415/1. Change of C0415/1 sets
C0008 = 255!

2 Digital output X3/A1

(DIGOUT1)

16

Ready for operation (DCTRL1−RDY)

A selection in C0117 is copied into
C0415/2. Change of C0415/2 sets
C0117 = 255!

3 (A) Digital output X3/A2

(DIGOUT2)

255

Not assigned (FIXED−FREE)

C0415

v

(cont.)

Possible digital signals for C0415

^ 7−73

0

Not assigned (FIXED−FREE)

1

Parameter set 2 or parameter set 4 is active
(DCTRL1−PAR−B0)

PAR−B1

PAR−B0

LOW

LOW

LOW

HIGH

HIGH

LOW

HIGH

HIGH

Active
PAR1
PAR2
PAR3
PAR4

2

Pulse inhibit active (DCTRL1−IMP)

3

I

max

limit reached (MCTRL1−IMAX)

(C0014 = −5−: torque setpoint reached)

4

Frequency setpoint reached
(DCTRL1−RFG1=NOUT)

5

Ramp function generator 1: input = output
(NSET1−RFG1−I=O)

RFG1 = ramp function generator − main
setpoint

6

Values have fallen below frequency threshold
Q

min

(f < C0017) (PCTRL1−QMIN)

LOW active

7

Output frequency = 0 (DCTRL1−NOUT=0)

8

Controller inhibit active (DCTRL1−CINH)

9 ... 12

Reserved

13

Group signal (DCTRL1−OH−PTC−LP1−FAN1−WARN):
Overtemperature warning (

J

max

− 5 °C)

(DCTRL1−OH−WARN)
or

Motor overtemperature warning

or

Set C0119 = 2 or C0119 = 5

Motor phase failure warning (DCTRL1−LP1−WARN)
or

Set C0597 = 2

Fan failure warning (DCTRL1−FAN1−WARN)
(only active with 8200 motec and C0608 = 1))

With 8200 vector, C0608 must be set to 0

14

DC bus overvoltage (DCTRL1−OV)

15

CCW rotation (DCTRL1−CCW)

16

Ready for operation (DCTRL1−RDY)

17

Parameter set 3 or parameter set 4 active
(DCTRL1−PAR−B1)

PAR−B1

PAR−B0

LOW

LOW

LOW

HIGH

HIGH

LOW

HIGH

HIGH

Active
PAR1
PAR2
PAR3
PAR4

18

Values have fallen below TRIP or Q

min

or pulse

inhibit (IMP) is active (DCTRL1−TRIP−QMIN−IMP)

LOW active

19

PTC warning (DCTRL1−PTC−WARN)

Set C0119 = 2 or C0119 = 5

Status of relay K

SR

Only with 8200 vector 15 ...90 kW, variant
"safe standstill":
HIGH = pulse inhibit active by "safe
standstill"
LOW = no pulse inhibit by "safe standstill"