Commissioning, Vector control – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 52
Commissioning
Vector control
5−11
L
EDB82MV752 EN 5.2
11.
Activate the control mode "vector control" (C0014 = 4)
Lenze setting: Linear V/f characteristic control (C0014 = 2)
E82ZBC014
z
y
w x
v
t
u
s
4
00 14
000
1
c
d
f
PS
p
Para
H/L
Subcode
Disp
Set
12.
Enter the motor data
See motor nameplate
A
Rated motor speed (C0087)
Lenze setting: 1390 rpm
B
Rated motor current (C0088)
Lenze setting: Depends on the controller
Enter the value for the motor connection type
(star/delta) selected!
C
Rated motor frequency (C0089)
Lenze setting: 50 Hz
D
Rated motor voltage (C0090)
Lenze setting: Depends on the controller
Enter the value for the motor connection type
(star/delta) selected!
E
Motor−cos
j (C0091)
Lenze setting: Depends on the controller
13.
Start the motor parameter identification (C0148)
Only when the motor is cold!
A
Ensure that the controller is inhibited
misc001
20
28
X3
}
Terminal X3/28 = LOW
B
Set C0148 = 1
Press
TV
C
Enable the controller
misc002
20
28
X3
·
Terminal X3/28 = HIGH
·
The identification starts:
– The segment
c
is off
– The motor consumes current and makes
a high−pitched" tone.
– The motor does not rotate!
D
If the segment
c
becomes active after approx. 30 s,
inhibit the controller once again.
misc001
20
28
X3
}
·
Terminal X3/28 = LOW
·
Identification is completed.
·
Calculated and stored:
– V/f rated frequency (C0015)
– Slip compensation (C0021)
– Motor stator inductance (C0092)
·
Measured and stored:
– Motor stator resistance (C0084) = Total
resistance of motor cable and motor
14.
If necessary, change other parameters
Activate e.g. JOG frequencies
(C0037, C0038, C0039) or
motor temperature monitoring
(C0119)
15.
Go to the
ALL
menu
A Check the fan monitoring setting under code C0608:
– for 8200 motec 0.25...0.37 kW and 0.55...2.2 kW:
C0608 = 0! (default setting)
– for 8200 motec 3...7.5 kW:
C0608 =1 (recommended) or C0608 = 2!
Stop!
Function must be activated during
commissioning! Otherwise, the controller may be
destroyed through overheating!
– for all other controllers:
C0608 = 0 ! (default setting)
B Select additional functions via codes, if necessary.
When all settings are complete:
16.
Select the setpoint
E.g. via potentiometer at
terminals 7, 8, 9
17.
Enable the controller
20
28
X3
misc002
Terminal X3/28 = HIGH
18.
The drive should now be running.
If the drive does not start, press
u
in
addition