Appendix, Code table – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual

Page 215

background image

Appendix

Code table

14−14

L

EDB82MV752 EN 5.2

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0007

v
uSEr

(cont.)

E4

E3

E2

E1

41

JOG1/3

DCB

TRIP set

DFIN1−ON

42

QSP

DCB

TRIP set

DFIN1−ON

43

CW/CCW

QSP

TRIP set

DFIN1−ON

44

UP

DOWN

PAR

DFIN1−ON

45

CW/CCW

QSP

PAR

DFIN1−ON

46

H/Re

PAR

QSP

JOG1/3

47

CW/QSP

CCW/QSP

H/Re

JOG1/3

48

PCTRL1− OFF

DCB

PCTRL1−I−OFF

DFIN1−ON

49

PCTRL1− OFF

JOG1/3

QSP

DFIN1−ON

50

PCTRL1− OFF

JOG1/3

PCTRL1−I−OFF

DFIN1−ON

51

DCB

PAR

PCTRL1−I−OFF

DFIN1−ON

255

Free configuration under C0410

Only display
Do not change C0007 since settings under
C0410 can be lost

C0008

v

Fixed configuration
− relay output K1
(relay, motec
version 151) or
Digital switching
output K1 (motec
versions 152, 153)

1

Change of C0008 is copied into C0415/1.
Free configuration in C0415/1 sets
C0008 = 255!

^ 7−73

0

Ready for operation (DCTRL1−RDY)

1

TRIP error message (DCTRL1−TRIP)

2

Motor is running (DCTRL1−RUN)

3

Motor is running / CW rotation (DCTRL1−RUN−CW)

4

Motor is running / CCW rotation
(DCTRL1−RUN−CCW)

5

Output frequency = 0 (DCTRL1−NOUT=0)

6

Frequency setpoint reached
(DCTRL1−RFG1=NOUT)

7

Values have fallen below frequency threshold
Q

min

(f < C0017) (PCTRL1−QMIN)

LOW active

8

I

max

limit reached (MCTRL1−IMAX)

C0014 = 5: torque setpoint reached

9

Overtemperature (

ϑ

max

−5 °C)

(DCTRL1−OH−WARN)

10

Values have fallen below TRIP or Q

min

or pulse

inhibit (IMP) (DCTRL1−TRIP−QMIN−IMP)

11

PTC warning (DCTRL1−PTC−WARN)

12

Apparent motor current < current threshold
(DCTRL1−IMOT

V−belt monitoring
Apparent motor current = C0054
Current threshold = C0156
Frequency threshold Q

min

= C0017

13

Apparent motor current < current threshold and
output frequency > Frequency threshold Q

min

(DCTRL1−(IMOT

14

Apparent motor current < current threshold and
ramp function generator 1: input = output
(DCTRL1−(IMOT

15

Motor phase failure warning (DCTRL1−LP1−WARN)

16

Minimum output frequency reached (f

£ C0010)

(PCTRL1−NMIN)

LOW active

255

Free configuration in C0415/1

Read only
Do not change C0008 since settings in
C0415/1 may get lost