Appendix

Code table

14−15

L

EDB82MV752 EN 5.2

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0009*

v

Controller address

1

1

{1}

99 Only for communication modules on the AIF

interface:

·

LECOM−A (RS232) E82ZBL

·

LECOM−A/B/LI 2102

·

PROFIBUS−DP 213x,

·

System bus (CAN) 217x

During operation with the E82ZAFCC
system bus function module the node
address must be set under C0350.

C0010

uSEr

Minimum output
frequency

0.00

0.00

à

14.5 Hz

{0.02 Hz}

650.00

·

C0010 is not effective with bipolar
setpoint selection (−10 V ... + 10 V)

·

C0010 only defines the analog input 1

·

As of software 3.5: If C0010 > C0011,
the drive does not start running with
controller enable.

à

Speed setting range 1 : 6 for Lenze
geared motors: Setting absolutely
required for operation with Lenze geared
motors.

^ 7−21

C0011

uSEr

Maximum output
frequency

50.00

7.50

à

87 Hz

{0.02 Hz}

650.00

C0012

uSEr

Acceleration time
main setpoint

5.00

0.00

{0.02 s}

1300.00 Reference: frequency change 0 Hz ...

C0011

·

Additional setpoint

ð C0220

·

Acceleration times can be activated via
digital signals

ð C0101

^ 7−24

C0013

uSEr

Deceleration time
main setpoint

5.00

0.00

{0.02 s}

1300.00 Reference: frequency change

C0011 ... 0 Hz

·

Additional setpoint

ð C0221

·

Deceleration times can be activated via
digital signals

ð C0103

^ 7−24

C0014

v

Operating mode

2

2

V/f characteristic control V ~ f
(linear characteristic with constant V

min

boost)

·

Commissioning is possible without
identifying motor parameters

·

Advantage of identification with C0148:

– Improved smooth running at low

speeds

– V/f rated frequency (C0015) and slip

(C0021) are calculated and saved.
They must not be entered

^ 7−2

3

V/f characteristic control V ~ f

2

(square−law characteristic with constant V

min

boost)

4

Vector control

In case of the first selection enter the
motor data and identify them with
C0148
Otherwise, commissioning is not
possible
When C0014 = 5, C0019 must be set = 0
(automatic DC injection brake is
deactivated)

5

Sensorless torque control with speed limitation

·

Torque setpoint via C0412/6

·

Speed limitation via setpoint 1 (NSET1−N1) if
C0412/1 is assigned, otherwise via maximum
frequency (C0011)

C0015

uSEr

V/f rated frequency

50.00

7.50

{0.02 Hz}

960.00

·

C0015 is calculated and stored under
C0148 when the motor parameters are
identified

·

Setting applies to all mains voltages
permitted

^ 7−4

^ 7−8

C0016

uSEr

V

min

boost

а

0.00

{0.01 %}

40.00

а

Depending on the controller

Setting applies to all mains voltages
permitted

^ 7−4

C0017

Frequency
threshold Q

min

0.00

0.00

{0.02 Hz}

650.00 Programmable frequency threshold

·

Reference: Setpoint

·

Signal output configuration under C0415

C0018

v

Switching
frequency

2

0

2 kHz sin

General rule:
The lower the switching frequency the

·

lower the power loss

·

higher the noise generation

Only operate mid−frequency motors at 8
kHz sin or 16 kHz sin (C0018 = 2 or 3)!

^ 7−14

1

4 kHz sin

2

8 kHz sin

low noise generation

3

16 kHz sin