Appendix, Code table – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 216
![background image](/manuals/566255/216/background.png)
Appendix
Code table
14−15
L
EDB82MV752 EN 5.2
Code
IMPORTANT
Possible settings
No.
Selection
Lenze
Name
C0009*
v
Controller address
1
1
{1}
99 Only for communication modules on the AIF
interface:
·
LECOM−A (RS232) E82ZBL
·
LECOM−A/B/LI 2102
·
PROFIBUS−DP 213x,
·
System bus (CAN) 217x
During operation with the E82ZAFCC
system bus function module the node
address must be set under C0350.
C0010
uSEr
Minimum output
frequency
0.00
0.00
à
14.5 Hz
{0.02 Hz}
650.00
·
C0010 is not effective with bipolar
setpoint selection (−10 V ... + 10 V)
·
C0010 only defines the analog input 1
·
As of software 3.5: If C0010 > C0011,
the drive does not start running with
controller enable.
à
Speed setting range 1 : 6 for Lenze
geared motors: Setting absolutely
required for operation with Lenze geared
motors.
^ 7−21
C0011
uSEr
Maximum output
frequency
50.00
7.50
à
87 Hz
{0.02 Hz}
650.00
C0012
uSEr
Acceleration time
main setpoint
5.00
0.00
{0.02 s}
1300.00 Reference: frequency change 0 Hz ...
C0011
·
Additional setpoint
ð C0220
·
Acceleration times can be activated via
digital signals
ð C0101
^ 7−24
C0013
uSEr
Deceleration time
main setpoint
5.00
0.00
{0.02 s}
1300.00 Reference: frequency change
C0011 ... 0 Hz
·
Additional setpoint
ð C0221
·
Deceleration times can be activated via
digital signals
ð C0103
^ 7−24
C0014
v
Operating mode
2
2
V/f characteristic control V ~ f
(linear characteristic with constant V
min
boost)
·
Commissioning is possible without
identifying motor parameters
·
Advantage of identification with C0148:
– Improved smooth running at low
speeds
– V/f rated frequency (C0015) and slip
(C0021) are calculated and saved.
They must not be entered
^ 7−2
3
V/f characteristic control V ~ f
2
(square−law characteristic with constant V
min
boost)
4
Vector control
In case of the first selection enter the
motor data and identify them with
C0148
Otherwise, commissioning is not
possible
When C0014 = 5, C0019 must be set = 0
(automatic DC injection brake is
deactivated)
5
Sensorless torque control with speed limitation
·
Torque setpoint via C0412/6
·
Speed limitation via setpoint 1 (NSET1−N1) if
C0412/1 is assigned, otherwise via maximum
frequency (C0011)
C0015
uSEr
V/f rated frequency
50.00
7.50
{0.02 Hz}
960.00
·
C0015 is calculated and stored under
C0148 when the motor parameters are
identified
·
Setting applies to all mains voltages
permitted
^ 7−4
^ 7−8
C0016
uSEr
V
min
boost
а
0.00
{0.01 %}
40.00
а
Depending on the controller
Setting applies to all mains voltages
permitted
^ 7−4
C0017
Frequency
threshold Q
min
0.00
0.00
{0.02 Hz}
650.00 Programmable frequency threshold
·
Reference: Setpoint
·
Signal output configuration under C0415
C0018
v
Switching
frequency
2
0
2 kHz sin
General rule:
The lower the switching frequency the
·
lower the power loss
·
higher the noise generation
Only operate mid−frequency motors at 8
kHz sin or 16 kHz sin (C0018 = 2 or 3)!
^ 7−14
1
4 kHz sin
2
8 kHz sin
low noise generation
3
16 kHz sin