background image

Technical data

Rated data at 230 V mains voltage

3−6

L

EDB82MV752 EN 5.2

3.2.2

Operation with increased rated power

Under the application conditions described here the controller can be operated in continuous
operation with a motor of higher performance. The overload capacity is reduced to 120 %.

·

Typical applications:
– Pumps with quadratic load characteristic

– Fan

·

Operation is only permissible

– in the mains voltage ranges mentioned
– at a switching frequency of 2 or 4 kHz

– with the prescribed fuses and cable cross−sections

Typical motor power
Three−phase asynchronous motor
(4−pole)

P

N

[kW]

0.37

0.55

P

N

[hp]

0.5

0.75

8200 motec

Type

E82MV251_2B

E82MV371_2B

Mains voltage

U

mains

[V]

1/N/PE AC 180 V − 0 % ... 264 V + 0 % ;

45 Hz − 0 % ... 65 Hz + 0 %

Data for operation on 1/N/PE AC 230 V

Rated mains current

I

mains

[A]

4.1

6.0

Rated output current at
switching frequency

2 kHz

I

N24

[A]

2.0

2.9

4 kHz

Max. permissible output
current for 60 s at
switching frequency

1)

2 kHz

I

max24

[A]

2.5

3.6

4 kHz

Output voltage

U

M

[V]

3~ 0 ... U

mains

/ 0 ... 650 Hz

Power loss (operation with I

N24

)

P

v

[W]

30

40

Dimensions

L x W x H [mm]

190 x 138 x 100

Weight

m [kg]

1.8

1.8

1)

Currents for periodic load change with 1 min overcurrent time with I

max

and 2 min base load time with 75 % I

Nx

Fuses and cable cross−sections

8200 motec

Operation with increased rated power

Installation acc. to EN 60204−1

Installation acc. to UL

1)

Type

System

Fuse

Circuit breaker

L1, L2, L3, PE

Fuse

L1, L2, L3, PE

FI

[kW]

[mm

2

]

[AWG]

E82MV251_2B

0.37

1/N/PE AC
180 ... 264 V;
45 ... 65 Hz

M10 A

C10 A

1.5

10 A

16

³ 30 mA

2)

E82MV371_2B

0.55

M10 A

C10 A

1.5

10 A

16

1)

Only use UL−approved cables, fuses, and fuse holders.
UL fuse: voltage 240 V, tripping characteristic "H", "K5" or "CC"

2)

Pulse current sensitive or universal−current sensitive earth−leakage circuit breaker

Observe national and regional regulations