Commissioning

V/f characteristic control

5−9

L

EDB82MV752 EN 5.2

14.

If you want to change other settings, please go to the

ALL

menu

Activate e.g. JOG frequencies
(C0037, C0038, C0039) or
motor temperature monitoring
(C0119)

15.

Go to the

ALL

menu

A Check the fan monitoring setting under code C0608:

– for 8200 motec 0.25...0.37 kW and 0.55...2.2 kW:

C0608 = 0! (default setting)

– for 8200 motec 3...7.5 kW:

C0608 =1 (recommended) or C0608 = 2!
Stop!
Function must be activated during
commissioning! Otherwise, the controller may be
destroyed through overheating!

– for all other controllers:

C0608 = 0 ! (default setting)

B Select additional functions via codes, if necessary.

When all settings are complete:

16.

Select the setpoint

E.g. via potentiometer at
terminals 7, 8, 9

17.

Enable the controller

20

28

X3

misc002

Terminal X3/28 = HIGH

18.

The drive should now be running.

If the drive does not start, press

u

in

addition