Appendix

Code table

14−42

L

EDB82MV752 EN 5.2

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0417*

v

Free configuration
of controller status
messages (1)

Output of digital signals to bus

The assignment is mapped to the

·

Controller status word 1 (C0150)

·

AIF status word (AIF−STAT)

·

FIF output word 1 (FIF−OUT.W1)

·

Output word 1 in CAN object 1
(CAN-OUT1.W1)

^ 7−79

1 Bit 0

1

Active parameter set
PAR−B0 active (DCTRL1−PAR−B0)

à

Fixed assignment to AIF when
operating with communication
modules INTERBUS 211x,
PROFIBUS−DP 213x or LECOM−A/B/LI
2102. Modifications are not allowed!

If you use function modules system bus
(CAN), INTERBUS, PROFIBUS−DP to FIF, all
bits are freely configurable.

2 Bit 1

2

Pulse inhibit active (DCTRL1−IMP)

à

3 Bit 2

3

I

max

limit reached (MCTRL1−IMAX)

(C0014 = −5−: Torque setpoint reached)

4 Bit 3

4

Frequency setpoint reached
(DCTRL1−RFG1=NOUT)

5 Bit 4

5

Ramp function generator 1: Input = output
(NSET1−RFG1−I=O)

6 Bit 5

6

Value below frequency threshold Q

min

(f < C0017)

(PCTRL1−QMIN)

7 Bit 6

7

Output frequency = 0 (DCTRL1−NOUT=0)

à

8 Bit 7

8

Controller inhibit active (DCTRL1−CINH)

à

9 Bit 8

9

à

11|10|9|8

0000
0001

Controller status
Controller initialization
Mains voltage off (at external supply of the
control section ofthe drive controller)

10 Bit 9

10

à

0010
0011
0100
0101
0110
0111
1000

Switch−on inhibit
Operation inhibited
Flying restart circuit active
DC−injection brake active
Operation enabled
Message active
Active error

11 Bit 10

11

à

12 Bit 11

12

à

13 Bit 12

13

Collective message:
(DCTRL1−OH−PTC−LP1−FAN1−WARN)

à

14 Bit 13

14

DC−bus overvoltage (DCTRL1−OV)

à

15 Bit 14

15

CCW rotation (DCTRL1−CCW)

16 Bit 15

16

Ready for operation (DCTRL1−RDY)

Digital signals possible for C0417 see C0415

C0418*

v

Free configuration
of controller status
messages (2)

Output of digital signals to bus

All bits can be freely configured
The assignment is mapped to the

·

Controller status word 2 (C0151)

·

FIF output word 2 (FIF−OUT.W2)

·

Output word 1 in the CAN object 2
(CAN−OUT2.W1)

^ 7−79

1 Bit 0

255

Not assigned (FIXED−FREE)

... ...

...

16 Bit 15

255

Not assigned (FIXED−FREE)

Digital signals possible for C0418 see C0415

C0419

v

Free configuration
of analog outputs

Output of analog signals to terminal

^ 7−59

1 X3/62 (AOUT1−IN)

0

Output frequency (MCTRL1−NOUT+SLIP)

A selection in C0111 is copied into
C0419/1. Change of C0419/1 sets
C0111 = 255!

2 (A) X3/63 (AOUT2−IN)

2

Apparent motor current (MCTRL1−IMOT)

3 (A) X3/A4 (DFOUT1−IN)

3

DC−bus voltage (MCTRL1−DCVOLT)

Frequency output: 50 Hz ... 10 kHz