Appendix, Code table – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 243
Appendix
Code table
14−42
L
EDB82MV752 EN 5.2
Code
IMPORTANT
Possible settings
No.
Selection
Lenze
Name
C0417*
v
Free configuration
of controller status
messages (1)
Output of digital signals to bus
The assignment is mapped to the
·
Controller status word 1 (C0150)
·
AIF status word (AIF−STAT)
·
FIF output word 1 (FIF−OUT.W1)
·
Output word 1 in CAN object 1
(CAN-OUT1.W1)
^ 7−79
1 Bit 0
1
Active parameter set
PAR−B0 active (DCTRL1−PAR−B0)
à
Fixed assignment to AIF when
operating with communication
modules INTERBUS 211x,
PROFIBUS−DP 213x or LECOM−A/B/LI
2102. Modifications are not allowed!
If you use function modules system bus
(CAN), INTERBUS, PROFIBUS−DP to FIF, all
bits are freely configurable.
2 Bit 1
2
Pulse inhibit active (DCTRL1−IMP)
à
3 Bit 2
3
I
max
limit reached (MCTRL1−IMAX)
(C0014 = −5−: Torque setpoint reached)
4 Bit 3
4
Frequency setpoint reached
(DCTRL1−RFG1=NOUT)
5 Bit 4
5
Ramp function generator 1: Input = output
(NSET1−RFG1−I=O)
6 Bit 5
6
Value below frequency threshold Q
min
(f < C0017)
(PCTRL1−QMIN)
7 Bit 6
7
Output frequency = 0 (DCTRL1−NOUT=0)
à
8 Bit 7
8
Controller inhibit active (DCTRL1−CINH)
à
9 Bit 8
9
à
11|10|9|8
0000
0001
Controller status
Controller initialization
Mains voltage off (at external supply of the
control section ofthe drive controller)
10 Bit 9
10
à
0010
0011
0100
0101
0110
0111
1000
Switch−on inhibit
Operation inhibited
Flying restart circuit active
DC−injection brake active
Operation enabled
Message active
Active error
11 Bit 10
11
à
12 Bit 11
12
à
13 Bit 12
13
Collective message:
(DCTRL1−OH−PTC−LP1−FAN1−WARN)
à
14 Bit 13
14
DC−bus overvoltage (DCTRL1−OV)
à
15 Bit 14
15
CCW rotation (DCTRL1−CCW)
16 Bit 15
16
Ready for operation (DCTRL1−RDY)
Digital signals possible for C0417 see C0415
C0418*
v
Free configuration
of controller status
messages (2)
Output of digital signals to bus
All bits can be freely configured
The assignment is mapped to the
·
Controller status word 2 (C0151)
·
FIF output word 2 (FIF−OUT.W2)
·
Output word 1 in the CAN object 2
(CAN−OUT2.W1)
^ 7−79
1 Bit 0
255
Not assigned (FIXED−FREE)
... ...
...
16 Bit 15
255
Not assigned (FIXED−FREE)
Digital signals possible for C0418 see C0415
C0419
v
Free configuration
of analog outputs
Output of analog signals to terminal
^ 7−59
1 X3/62 (AOUT1−IN)
0
Output frequency (MCTRL1−NOUT+SLIP)
A selection in C0111 is copied into
C0419/1. Change of C0419/1 sets
C0111 = 255!
2 (A) X3/63 (AOUT2−IN)
2
Apparent motor current (MCTRL1−IMOT)
3 (A) X3/A4 (DFOUT1−IN)
3
DC−bus voltage (MCTRL1−DCVOLT)
Frequency output: 50 Hz ... 10 kHz