Appendix

Code table

14−27

L

EDB82MV752 EN 5.2

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0225
(A)

Acceleration time −
process controller
setpoint
(PCTRL1−SET1)

0.00

0.00

{0.02 s}

1300.00 Acceleration encoder for process controller

setpoint = PCTRL1−RFG2

C0226
(A)

Deceleration time −
process controller
setpoint
(PCTRL1−SET1)

0.00

0.00

{0.02 s}

1300.00

C0228
(A)

Unhide time −
process controller

0.000

0.000

{0.001 s}

32.000 0.000 = Process controller output is

transferred without unhiding

C0229
(A)

Hide time − process
controller

0.000

0.000

{0.001 s}

32.000 0.000 = Fading−off" switched off (C0241)

C0230
(A)

Min. limit process
controller output

−100.0

−200.0

{0.1 %}

200.0 Asymmetric limit of process controller

output ref. to C0011

·

If value falls below C0230 or exceeds
C0231:

– Output signal PCTRL1−LIM = HIGH

after time set under C0233

·

Set C0231 > C0230

C0231
(A)

Max. limit process
controller output

100.0

−200.0

{0.1 %}

200.0

C0232
(A)

Offset inverse
characteristic
process controller

0.00

−200.0

{0.1 %}

200.0 Ref. to C0011

C0233*
(A)

Delay
PCTRL1−LIM=HIGH

0.000

0.000

{0.001 s}

65.000 "Debouncing" of digital output signal

PCTRL1−LIM (limit for process controller
output exceeded)

·

Sets PCTRL1−LIM = HIGH if the following
still applies after time set:

– Value below C0230 or higher than

C0231

·

Transition HIGH

ð LOW without delay

C0234*
(A)

Delay
PCTRL1−SET=ACT

0.000

0.000

{0.001 s}

65.000 "Debouncing" of digital output signal

PCTRL1−SET=ACT (process controller
setpoint = process controller actual value)

·

Sets PCTRL1−SET=ACT = HIGH if the
following still applies after time set:

– Difference between PCTRL1−SET and

PCTRL1−ACT is below threshold
under C0235

·

Transition HIGH

ð LOW without delay

C0235*
(A)

Difference
threshold
PCTRL1−SET=ACT

0.00

0.00

{0.01 Hz}

650.00 Threshold for the digital output signal

PCTRL1−SET=ACT (process controller
setpoint = process controller actual value)

·

Difference between PCTRL1−SET and
PCTRL1−ACT is within limits under
C0235:

– PCTRL1−SET=ACT = HIGH after time

set under C0234

C0236
(A)

Acceleration time −
minimum frequency
limitation

0.00

0.00

{0.02 s}

1300.00 Ref. to C0011

Minimum frequency limitation = C0239

^ 7−21

C0238

v

Frequency
precontrol

2

0

No precontrol (only process controller)

Process controller has full influence

^ 7−50

^ 7−53

1

Precontrol (total setpoint + process controller)

Process controller has limited influence

2

No precontrol (only total setpoint)

Process controller has no influence (not
active)

Total setpoint (PCTRL1−SET3) = Main
setpoint + additional setpoint

C0239

Lowest frequency
limit

−650.00 −650.00

{0.02 Hz}

650.00

·

The value does not fall below limit
independently of the setpoint.

·

If the minimum frequency limitation is
active, the automatic DC−injection brake
(auto DCB) must be deactivated (C0019
= 0 or C0106 = 0).

^ 7−21