Function library

Individual grouping of drive parameters − The menu

USEr

7−95

L

EDB82MV752 EN 5.2

7.16

Individual summary of drive parameters in the user menu

Description

·

Fast access to 10 codes

·

Individual combination of 10 codes most important for your application.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze

Selection

C0517*

v

User menu

·

After mains switching or when using the
function

g

the code from C0517/1

will be displayed.

·

In Lenze setting, the user menu contains
the most important codes for starting−up
the control mode "V/f characteristic
control with linear characteristic"

·

When the password protection is
activated, only the codes entered under
C0517 are freely accessible.

·

Enter the required code numbers in the
subcodes.

Codes, which are only active when
being used together with an
Application−I/O, cannot be entered!

^ 7−95

1 Memory 1

50

C0050

Output frequency (MCTRL1−NOUT)

2 Memory 2

34

C0034

Analog setpoint selection range

3 Memory 3

7

C0007

Fixed configuration − digital input signals

4 Memory 4

10

C0010

Minimum output frequency

5 Memory 5

11

C0011

Maximum output frequency

6 Memory 6

12

C0012

Acceleration time main setpoint

7 Memory 7

13

C0013

Deceleration time main setpoint

8 Memory 8

15

C0015

V/f rated frequency

9 Memory 9

16

C0016

U

min

boost

10 Memory 10

2

C0002

Parameter set transfer

User menu adaptation

Enter the required code number or subcode number into the subcodes under C0517.

)

Note!

Use the user menu to select "tailored" codes for your application to be used by
your personnel if the password protection is activated additionally. Your personnel
can only change codes listed in the user menu.

Example: Select speed via keypad

The personnel operating a transportation system shall be able to change the speed of the conveyor
using the keypad. The speed is set and indicated in "rpm":

User menu configuration

1. Assign C0140 to memory 1 of the user menu (C0517/1 = 140)

2. Delete all other entries from the user menu (C0517/2 ... C0517/10 = 0)

3. Convert the value indicated under C0140 into "rpm" using C0500/C0501

(

^ 7−86)

4. Activate the password protection (C0094 > 0)

5. The current conveyor speed will be indicated after the keypad has been attached or power

on.

6. Use

x

to activate the function

i

and to change the speed during operation using the

yz

keys. The speed set last will be stored when the mains is switched off.