Function library, Thermal motor monitoring, error detection – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual

Page 154

background image

Function library

Thermal motor monitoring, error detection

7−83

L

EDB82MV752 EN 5.2

The controller switches off with fault OC6, if the apparent motor current is higher than the rated motor
current over a longer period of time.

60

180

240

300

360

t [s]

0.5

0

0

1.0

1.5

2.0

C0054

I

r

120

f = 0 Hz

f = 20 Hz

f > 40 Hz

I x 100 %

I

r

N

C0120 <

I x 100 %

I

r

N

C0120 =

I x 100 %

I

r

N

C0120 >

8200vec523

Fig. 7−16

Tripping characteristic of I

2

t monitoring

f

Output frequency

t

Time to trip

I

r

Rated controller current at a chopper frequency of 8 kHz

I

r

Rated motor current

C0054

Apparent motor current

Example:

C0120

+

I

r

I

N

@ 100 %

C0054 = 1.5 x rated motor current
The controller switches off at output frequencies f > 40 Hz after approx. 60 s with fault OC6.

Tip

·

To prevent motors with forced ventilation from starting too early, this function can be
deactivated.

·

The current limits C0022 and C0023 only have indirect influence on the I

2

t calculation. It is

possible to prevent motor operation with a maximum of possible load with settings under
C0022 and C0023.

)

Note!

If the controller operates at increased rated power, the I

2

t monitoring starts if C0120

is set lower than 100 %.