Process controller, current limitation controller

7−54

L

EDB82MV752 EN 5.2

Process controller setpoint = C0181

C0145 = 1

Process controller setpoint = Value under C0181.

·

Applications are e.g. dancer controls, pressure controls and flow rate controls

·

Activate the automatic DC−injection brake (auto DCB) with C0019 = 0 or C0106 = 0

·

C0181 is the same in all parameter sets.

C0145 = 2

Process controller setpoint = Freely configured signal via C0412/4.

·

The process controller setpoint (PCTRL1−SET1) must be linked with an analog input signal
under C0412/4.

·

Use C0138 to display the current process controller setpoint.

·

The setpoint acts directly on the process controller.

)

Note!

If you do not link an analog input signal with the process controller setpoint under
C0412/4, the process controller setpoint can be directly selected under C0138.

7.8.3

Actual value selection for the process controller

Description

The actual value is the process feedback signal (e.g. from a pressure encoder or a speed encoder).

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze

Selection

C0051*

Output frequency
with slip
compensation
(MCTRL1−NOUT
+SLIP) or
act. process
controller value
(PCTRL1−ACT)

−650.00

{0.02 Hz}

650.00

The value set will be lost when
switching the mains!
Operation without process controller
(C0238 = 2):

·

Display only: Output frequency with slip
compensation (MCTRL1−NOUT+SLIP)

Operation with process controller
(C0238 = 0, 1):

·

Selection, if C0412/5 = FIXED−FREE (not
assigned)

·

Display if C0412/5 is linked with a signal
source

^ 7−54

Activation

The actual process controller value (PCTRL1−ACT) must be linked with an analog input signal under
C0412/5.

Use C0051 to display the current actual process controller value.

)

Note!

If you do not link an analog input signal with the actual process controller value
under C0412/5, the actual process controller value can be directly selected under
C0051.