Function library, Free connection of digital signals, message output – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 151
Function library
Free connection of digital signals, message output
7−80
L
EDB82MV752 EN 5.2
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0417*
v
Free configuration
of controller status
messages (1)
Output of digital signals to bus
The assignment is mapped to the
·
Controller status word 1 (C0150)
·
AIF status word (AIF−STAT)
·
FIF output word 1 (FIF−OUT.W1)
·
Output word 1 in CAN object 1
(CAN-OUT1.W1)
^ 7−79
1 Bit 0
1
Active parameter set
PAR−B0 active (DCTRL1−PAR−B0)
à
Fixed assignment to AIF when
operating with communication
modules INTERBUS 211x,
PROFIBUS−DP 213x or LECOM−A/B/LI
2102. Modifications are not allowed!
If you use function modules system bus
(CAN), INTERBUS, PROFIBUS−DP to FIF, all
bits are freely configurable.
2 Bit 1
2
Pulse inhibit active (DCTRL1−IMP)
à
3 Bit 2
3
I
max
limit reached (MCTRL1−IMAX)
(C0014 = −5−: Torque setpoint reached)
4 Bit 3
4
Frequency setpoint reached
(DCTRL1−RFG1=NOUT)
5 Bit 4
5
Ramp function generator 1: Input = output
(NSET1−RFG1−I=O)
6 Bit 5
6
Value below frequency threshold Q
min
(f < C0017)
(PCTRL1−QMIN)
7 Bit 6
7
Output frequency = 0 (DCTRL1−NOUT=0)
à
8 Bit 7
8
Controller inhibit active (DCTRL1−CINH)
à
9 Bit 8
9
à
11|10|9|8
0000
0001
Controller status
Controller initialization
Mains voltage off (at external supply of the
control section ofthe drive controller)
10 Bit 9
10
à
0010
0011
0100
0101
0110
0111
1000
Switch−on inhibit
Operation inhibited
Flying restart circuit active
DC−injection brake active
Operation enabled
Message active
Active error
11 Bit 10
11
à
12 Bit 11
12
à
13 Bit 12
13
Collective message:
(DCTRL1−OH−PTC−LP1−FAN1−WARN)
à
14 Bit 13
14
DC−bus overvoltage (DCTRL1−OV)
à
15 Bit 14
15
CCW rotation (DCTRL1−CCW)
16 Bit 15
16
Ready for operation (DCTRL1−RDY)
Digital signals possible for C0417 see C0415
C0418*
v
Free configuration
of controller status
messages (2)
Output of digital signals to bus
All bits can be freely configured
The assignment is mapped to the
·
Controller status word 2 (C0151)
·
FIF output word 2 (FIF−OUT.W2)
·
Output word 1 in the CAN object 2
(CAN−OUT2.W1)
^ 7−79
1 Bit 0
255
Not assigned (FIXED−FREE)
... ...
...
16 Bit 15
255
Not assigned (FIXED−FREE)
Digital signals possible for C0418 see C0415
Signal linkage
The process data output words are linked with internal signals by entering the selection figure of the
internal signal in the corresponding subcode C0417 and C0418. C0417 and C0418 can be different
for the parameter sets.
Examples
·
C0417/4
ð
16: The status message Ready for operation" is the signal source for bit 3.
·
C0418/5
ð
101: Bit 2 of CAN−IN2.W1 is the signal source for bit 4.