Installation

Electrical installation − Important notes

4−6

L

EDB82MV752 EN 5.2

4.2.1.7

Specification of the cables used

Power terminals

·

The cables used must comply with the approvals required for the application (e.g. UL).

·

Use low−capacitance motor cables. Capacitance per unit length:
– Core/core

£ 75 pF/m

– Core/shield

£ 150 pF/m

·

Max. permissible motor cable length without external measures:
– unshielded: 10 m

– shielded: 10 m

Control connections

·

Control cables must always be shielded to prevent interference injections.

Shielded cables

The efficiency of shielded cables is determined by

·

a good shield connection
– a contact surface as large as possible.

·

a low shield resistance:

– only use shields with tin or nickel−plated copper braid!
– shields made of steel braid are not suitable.

·

the overlap rate of the braid:
– at least 70 to 80 % with an overlap angle of 90°.