Function library

Selection of control mode, optimisation of operating behaviour

7−19

L

EDB82MV752 EN 5.2

)

Note!

l

The flying−restart circuit must not be used if several motors with different rotating
masses are connected to a controller.

l

The flying restart method is safe and reliable for drives with great rotating masses.

l

With machines with low moments of inertia and small friction, the motor can
restart for a short time or reverse after controller enable.

·

The controller only searches the given direction of rotation.

·

The controller calculates the output frequency required for the current speed of the idling
motor, is connected and accelerates the motor until it reaches its setpoint.

Adding a signal (C0143 = 2, C0143 = 3)

The controller adds the output frequency corresponding to the frequency setpoint or the actual
process controller value.

)

Note!

The actual process controller value must only be set if a speed−proportional signal is
available in C0412/5!

Tip

If the flying−restart circuit is not required for every drive start, but only after mains reconnection:

·

Bridge X3/28 with HIGH level and start the controller with the function QSP" (C0142 = 3 and
C0106 = 0 s).

·

The flying−restart circuit is now only activated for for the first mains connection.

7.3.2

Controlled deceleration after mains failure/mains disconnection

)

Note!

This function cannot be used with a 8200 motec!