Technical data – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 25
Technical data
Rated data at 400/500 V mains voltage
3−10
L
EDB82MV752 EN 5.2
Fuses and cable cross−sections
8200 motec
Operation with increased rated power
Installation acc. to EN 60204−1
Installation acc. to UL
1)
Type
System
Fuse
Circuit breaker
L1, L2, L3, PE
Fuse
L1, L2, L3, PE
FI
[kW]
[mm
2
]
[AWG]
E82MV551_4B
0.75
3/PE AC
320 ... 440 V;
45 ... 65 Hz
M6 A
B6 A
1
5 A
18
³ 30 mA
2)
E82MV751_4B
1.1
M6 A
B6 A
1
5 A
18
E82MV152_4B
2.2
M10 A
B10 A
1.5
10 A
16
E82MV222_4B
3.0
M10 A
B10 A
1.5
10 A
16
E82MV302_4B
4.0
M16 A
B16 A
2.5
15 A
14
³ 300 mA
2)
E82MV402_4B
5.5
M20 A
B20 A
4.0
20 A
12
E82MV552_4B
7.5
M32 A
B32 A
6.0
25 A
10
1)
Only use UL−approved cables, fuses, and fuse holders.
UL fuse: voltage 500 ... 600 V, tripping characteristic "H", "K5" or "CC"
2)
Universal−current sensitive earth−leakage circuit breaker
Observe national and regional regulations
Current derating
Depending on the operating conditions and the use of the 8200 motec, the types E82MV302_4B to
EMV552_4B may require a reduction of the rated output current in continuous operation:
8200 motec mounted on...
Current derating
...Lenze motor/forced ventilated geared motor
not required
...Lenze motor/self−ventilated geared motor
see illustration below
...Lenze motor/self−ventilated geared motor with E82ZMV supplementary module
not required
...no Lenze motor/geared motor Þ E82ZMV supplementary module is always required
not required
...the wall (wall mounting)
Þ E82ZMV supplementary module is always required
not required
0,1
10
20
30
40
50
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1
f [Hz]
I/I
N
E8
2M
V3
02_
4B
E8
2M
V4
02
_4
B
E8
2M
V5
52
_4
B
Fig. 3−2
Reduction of the rated output current in continuous operation at 40°C ambient temperature and a switching frequency of
4 kHz
I
Reduced output current 8200 motec
I
N
Rated output current 8200 motec at a switching frequency of 4 kHz
f