beautypg.com

Mains types/mains conditions, Installation, 3 mains types/mains conditions – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual

Page 29

background image

Installation

Electrical installation − Important notes

4−4

L

EDB82MV752 EN 5.2

4.2.1.3

Mains types/mains conditions

Please observe the restrictions of each mains type!

System

Controller operation

Notes

with earthed neutral
(TT/TN systems)

No restrictions

Comply with the rated data of the
controllers.

with isolated neutral
(IT systems)

possible if the controller is protected in the event of an earth fault in the
mains supply

·

by suitable equipment which detect the earth fault and

·

the controller is directly disconnected from the mains

In the event of an earth fault at the
inverter output, a safe operation
cannot be ensured.

4.2.1.4

Operation on public supply systems (compliance with EN 61000−3−2)

The European standard EN 61000−3−2 stipulates limit values for harmonic currents in the supply
system. Non−linear consumers (e.g. frequency inverters) cause harmonic currents which "interfere"
the supplying mains and may disturb other consumers. This standard helps to ensure the high quality
of public mains systems and reduce the mains load.

Tip!

The standard only applies to public mains systems. Mains systems with an own transformer station
as common in industry are not public. Thus, the standard does not apply to them.

If a device or machine consists of several components, the limit values defined in the standard apply
to the entire unit.

If you observe all measures given, the controllers comply with the limit values according to
EN 61000−3−2. The machine/system manufacturer is responsible for the compliance with the
requirements for the machine/system:

Supply voltage

Power

Measure

8200 motec

[V]

[kW]

E82MV251_2B

1/N/PE AC 230 V

0.25

Use ELN1−0900H005 mains choke

E82MV371_2B

0.37

E82MV551_4B

3/PE AC 400 V

0.55

Use EZN3A1500H003 mains choke

E82MV751_4B

0.75