beautypg.com

Function library – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual

Page 76

background image

Function library

Selection of control mode, optimisation of operating behaviour

7−5

L

EDB82MV752 EN 5.2

Setting the V/f characteristic

Under C0014 select the V/f characteristic suitable for your application.

)

Note!

The following must be observed when operating drives with square−law V/f
characteristic:

l

High moments of inertia reduce the acceleration of the drive.

l

This drive behaviour can be avoided by using the linear V/f characteristic via the
parameter set changeover during the acceleration.

Setting of V/f rated frequency

10

The V/f rated frequency determines the slope of the V/f characteristic and has considerable
influence on the current, torque and power performance of the motor.

·

The setting under C0015 applies to all admitted mains voltages.

·

The internal mains voltage compensation compensates deviations in the mains during
operation. Therefore, they do not have to be considered for the setting of C0015.

·

Depending on the settings under C0015 it can be necessary to adapt the maximum output
frequency under C0011 to ensure that the entire speed range will be used.

·

The V/f rated frequency depends on the rated controller voltage, the rated motor voltage, and
the rated motor frequency:

C0015 [Hz]

+

U [V]

U

r

[V]

@ f

r

[Hz]

V

400 V for E82xVxxxK4C types

V

230 V for E82xVxxxK2C types

V

r

Rated motor voltage depending on type of connection, see nameplate

f

r

Rated motor frequency according to nameplate

)

Note!

The identification of the motor parameters calculates C0015 and automatically
saves the value.