beautypg.com

2 rated data at a mains voltage of 230 v, 1 operation with rated power (normal operation), Rated data at a mains voltage of 230 v – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual

Page 20: Operation with rated power (normal operation), Technical data, Rated data at 230 v mains voltage

background image

Technical data

Rated data at 230 V mains voltage

3−5

L

EDB82MV752 EN 5.2

3.2

Rated data at a mains voltage of 230 V

3.2.1

Operation with rated power (normal operation)

Typical motor power
Three−phase asynchronous motor
(4−pole)

P

N

[kW]

0.25

0.37

P

N

[hp]

0.34

0.5

8200 motec

Type

E82MV251_2B

E82MV371_2B

Mains voltage

U

mains

[V]

1/N/PE AC 180 V − 0 % ... 264 V + 0 % ;

45 Hz − 0 % ... 65 Hz + 0 %

Data for operation at 1/N/PE AC 230 V

Rated mains current

I

mains

[A]

3.4

5.0

Rated output current at
switching frequency

2 kHz

I

N24

[A]

2)

2.0

2.9

4 kHz

8 kHz

I

N8

[A]

1.7

2.4

16 kHz

I

N16

[A]

1.1

1.6

Max. permissible output
current for 60 s at
switching frequency

1)

2 kHz

I

max24

[A]

2.5

3.6

4 kHz

8 kHz

I

max8

[A]

2.5

3.6

16 kHz

I

max16

[A]

1.6

1.4

Output voltage

U

M

[V]

3~ 0 ... U

mains

/ 0 ... 650 Hz

Power loss (operation with I

N8

)

P

v

[W]

30

40

Dimensions

L x W x H [mm]

190 x 138 x 100

Weight

m [kg]

1.8

1.8

Bold print = data for operation at a switching frequency of 8 kHz (Lenze setting)

1)

Currents for periodic load change: 1 min overcurrent time with I

max

and 2 min base load time with 75 % I

Nx

2)

Under different operating conditions possible for some types: Operation with increased rated output current with the same load change
cycle (

^ 3−6)

Fuses and cable cross−sections

8200 motec

Normal operation

Installation acc. to EN 60204−1

Installation acc. to UL

1)

Type

System

Fuse

Circuit breaker

L1, L2, L3, PE

Fuse

L1, L2, L3, PE

FI

[kW]

[mm

2

]

[AWG]

E82MV251_2B

0.25

1/N/PE AC
180 ... 264 V;
45 ... 65 Hz

M10 A

C10 A

1.5

10 A

16

³ 30 mA

2)

E82MV371_2B

0.37

M10 A

C10 A

1.5

10 A

16

1)

Only use UL−approved cables, fuses, and fuse holders.
UL fuse: voltage 240 V, tripping characteristic "H", "K5" or "CC"

2)

Pulse current sensitive or universal−current sensitive earth−leakage circuit breaker