Appendix

Code table

14−21

L

EDB82MV752 EN 5.2

Code

IMPORTANT

Possible settings

No.

Selection

Lenze

Name

C0114

v

Level inversion −
digital inputs

0

0

Level inversion switched off

·

By entering the sum of the selected
values you can invert several inputs.

·

C0114 and C0411 are the same

·

The "Change over parameter set"
cannot be inverted!

1

E1 inverted

2

E2 inverted

4

E3 inverted

8

E4 inverted

16

E5 inverted

Only application I/O

32

E6 inverted

Only application I/O

64

T1/T2 inverted

Only connect potential−free switches to
T1/T2.
T1/T2 is active when the switch is open.

C0117

v

Fixed configuration
of digital output A1
(DIGOUT1)

0

Changes of C0117 will be copied to
C0415/2. Free configuration under
C0415/2 sets C0117 =255!

^ 7−73

0 ... 16

see C0008

255

Free configuration under C0415/2

Only display
Do not change C0117 since settings under
C0415/2 can be lost

C0119

v

−25−

Configuration of
motor temperature
monitoring (PTC
input) / earth fault
detection

0

0

PTC input not active

Earth fault detection
active

·

Signal output configuration under C0415

·

If several parameter sets are used, the
monitoring must be separately adjusted
for each parameter set.

·

Deactivate the earth fault detection, if it
has been activated unintentionally.

·

If the earth fault detection is active, the
motor starts after controller enable with
a delay of approx.40 ms.

^ 7−84

1

PTC input active,
TRIP set

2

PTC input active,
Warning set

3

PTC input not active

Earth fault detection
inactive

4

PTC input active,
TRIP set

5

PTC input active,
Warning set

C0120

I

2

t switch−off

0

0
= not active

{1 %}

200 Reference: Apparent motor current (C0054)

Ref. to active motor current (C0056)
possible, see C0310

^ 7−82

C0125*

v

Baud rate

0

LECOM

System bus (CAN) 217x

Only for communication modules on the AIF
interface:

·

LECOM−A (RS232) E82ZBL

·

LECOM−A/B/LI 2102

·

System bus (CAN) 217x

During operation with the E82ZAFCC
system bus function module the baud
rate must be set under C0351.

0

9600 baud

500 kbaud

1

4800 baud

250 kbaud

2

2400 baud

125 kbaud

3

1200 baud

50 kbaud

4

19200 baud

1000 kbaud

C0126*

v

Response in the
event of a
communication
error

10

Monitored communication channel

By entering the sum of the selected values
you can activate a monitoring combination

0

All monitoring is deactivated

1

Process channel of the AIF interface

Communication abort at active monitoring
activates TRIP CE0

2

Internal communication between function module
on FIF and controller

Communication abort at active monitoring
activates TRIP CE5

4

Communication (bus OFF) at operation with
system bus function module (CAN) on FIF

Communication abort at active monitoring
activates TRIP CE6

8

Remote parameter setting via C0370 at operation
with function module system bus (CAN) on FIF

Communication abort at active monitoring
activates TRIP CE7

C0127

v

Setpoint selection

0

0

Absolute setpoint selection in Hz via C0046 or
process data channel

1

Setpoint selection normalised via C0141 (0... 100
%) or process data channel (

±16384 = C0011)

C0128

Service code

Modifications only by Lenze Service!