Appendix, Code table – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 222
Appendix
Code table
14−21
L
EDB82MV752 EN 5.2
Code
IMPORTANT
Possible settings
No.
Selection
Lenze
Name
C0114
v
Level inversion −
digital inputs
0
0
Level inversion switched off
·
By entering the sum of the selected
values you can invert several inputs.
·
C0114 and C0411 are the same
·
The "Change over parameter set"
cannot be inverted!
1
E1 inverted
2
E2 inverted
4
E3 inverted
8
E4 inverted
16
E5 inverted
Only application I/O
32
E6 inverted
Only application I/O
64
T1/T2 inverted
Only connect potential−free switches to
T1/T2.
T1/T2 is active when the switch is open.
C0117
v
Fixed configuration
of digital output A1
(DIGOUT1)
0
Changes of C0117 will be copied to
C0415/2. Free configuration under
C0415/2 sets C0117 =255!
^ 7−73
0 ... 16
see C0008
255
Free configuration under C0415/2
Only display
Do not change C0117 since settings under
C0415/2 can be lost
C0119
v
−25−
Configuration of
motor temperature
monitoring (PTC
input) / earth fault
detection
0
0
PTC input not active
Earth fault detection
active
·
Signal output configuration under C0415
·
If several parameter sets are used, the
monitoring must be separately adjusted
for each parameter set.
·
Deactivate the earth fault detection, if it
has been activated unintentionally.
·
If the earth fault detection is active, the
motor starts after controller enable with
a delay of approx.40 ms.
^ 7−84
1
PTC input active,
TRIP set
2
PTC input active,
Warning set
3
PTC input not active
Earth fault detection
inactive
4
PTC input active,
TRIP set
5
PTC input active,
Warning set
C0120
I
2
t switch−off
0
0
= not active
{1 %}
200 Reference: Apparent motor current (C0054)
Ref. to active motor current (C0056)
possible, see C0310
^ 7−82
C0125*
v
Baud rate
0
LECOM
System bus (CAN) 217x
Only for communication modules on the AIF
interface:
·
LECOM−A (RS232) E82ZBL
·
LECOM−A/B/LI 2102
·
System bus (CAN) 217x
During operation with the E82ZAFCC
system bus function module the baud
rate must be set under C0351.
0
9600 baud
500 kbaud
1
4800 baud
250 kbaud
2
2400 baud
125 kbaud
3
1200 baud
50 kbaud
4
19200 baud
1000 kbaud
C0126*
v
Response in the
event of a
communication
error
10
Monitored communication channel
By entering the sum of the selected values
you can activate a monitoring combination
0
All monitoring is deactivated
1
Process channel of the AIF interface
Communication abort at active monitoring
activates TRIP CE0
2
Internal communication between function module
on FIF and controller
Communication abort at active monitoring
activates TRIP CE5
4
Communication (bus OFF) at operation with
system bus function module (CAN) on FIF
Communication abort at active monitoring
activates TRIP CE6
8
Remote parameter setting via C0370 at operation
with function module system bus (CAN) on FIF
Communication abort at active monitoring
activates TRIP CE7
C0127
v
Setpoint selection
0
0
Absolute setpoint selection in Hz via C0046 or
process data channel
1
Setpoint selection normalised via C0141 (0... 100
%) or process data channel (
±16384 = C0011)
C0128
Service code
Modifications only by Lenze Service!