Process controller, current limitation controller

7−53

L

EDB82MV752 EN 5.2

7.8.2

Setpoint selection for the process controller

Description

Selection of a frequency setpoint for the process controller, e.g. for

·

the dancer position for a dancer position control in a line drive.

·

the pressure setpoint for a pressure control.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze

Selection

C0138*

Process controller
setpoint 1
(PCTRL1−SET1)

0.00

−650.00

{0.02 Hz}

650.00

The value set will be lost when
switching the mains!

·

Selection if C0412/4 = FIXED−FREE

·

Display if C0412/4

¹ FIXED−FREE

^ 7−53

C0181*

Process controller
setpoint 2
(PCTRL1−SET2)

0.00

−650.00

{0.02 Hz}

650.00

^ 7−53

C0145*

v

Process controller
setpoint source

0

0

Total setpoint (PCTRL1−SET3)

Main setpoint + additional setpoint

^ 7−53

1

C0181 (PCTRL1−SET2)

·

Setpoint selection not possible via

– JOG values

j

function of the keypad

– C0044, C0046 and C0049
– in connection with manual/remote

changeover, skip frequencies, ramp
function generator, additional setpoint

·

Activate the automatic DC−injection
brake (auto DCB) with C0019 = 0 or
C0106 = 0

2

C0412/4 (PCTRL1−SET1)

Selection

Process controller setpoint = Total setpoint

C0145 = 0

Process controller setpoint = Total setpoint (PCTRL1−SET3)

Select C0145 = 0 if the setpoint is to be selected

·

via JOG values,

·

via keypad (C0140, function

j),

·

for operation with manual/remote changeover, skip frequencies, ramp function generator or
additional setpoint,

·

via parameter channel (C0044, C0046, C0049).