Technical data

General data/operating conditions

3−4

L

EDB82MV752 EN 5.2

Inputs and outputs

Analog
inputs/outputs

with standard I/O

1 input, optionally bipolar
1 output

with application I/O

2 inputs, optionally bipolar
2 outputs

Digital
inputs/outputs

with standard I/O

4 inputs, optionally 1 frequency input, single−track 0 ... 10 kHz / two−track 0...1 kHz; 1 input for controller inhibit
1 output

with application I/O

6 inputs, optionally 1 frequency input, single−track / two−track 0 ... 102.4 kHz; 1 input for controller inhibit
2 outputs, 1 frequency output 50 Hz ... 10 kHz

Cycle times

digital inputs

1 ms

digital outputs

4 ms

analog inputs

2 ms

analog outputs

4 ms (smoothing time:

t = 10 ms)

Relay output (device version 151)

Changeover contact, AC 250 V/3 A, DC 24 V/2 A ... 240 V/0.22 A

digital switching output
(device versions 152 and 153)

DC 24 V ext./50 mA or DC 20 V int./10 mA

Operation in generator mode
(monitored internally)

Integrated brake transistor
external brake resistors: (