Rockwell Automation 20Y PowerFlex 700H, 700S, and 700AFE Drive Fan Systems, Frames 9...14 User Manual
Page 43
Rockwell Automation Publication PFLEX-IN029B-EN-P - August 2014
43
PowerFlex 700H and 700S Drives - Frame 9 Procedures
Chapter 1
21.
Secure the fan inverter cover to the drive using the M4 x 8 mm
POZIDRIV screw.
22.
Install the lower protective cover in the reverse order of removal. See
Remove the Lower Protective Cover on page
.
23.
Remove the backing from the drive modification label and attach the label,
in a clearly visible location, to the front of the drive.
24.
Write “DC fan retrofit” and the installation date on the label.
Main AC Fan (20-PP01080) and Main DC Fan (SK-Y1-DCFAN1) Assembly
Removal and Installation
Follow these steps to measure the resistance between the main fan supply wires
and remove and replace the main fan, if necessary.
Notes:
•
To identify which fan is installed in your drive, see Fan Inverter System
Block Diagrams on page
.
•
For AC fan systems, the sheet metal bracket is available as a spare part (SK-
H1-FR9BRKT). See page
for details. For DC fan systems, the sheet
metal bracket is only available as part of the retrofit kit (SK-H1-
DCFANRETROFIT-F9). See page
for details.
•
The main fan replacement kit only contains the fan motor and impeller
assembly. Therefore, if the sheet metal mounting bracket is not available as
a spare part for your fan system, it must be reused.
1
2
3
4
ON
X6
X1
X4
X5
X7
S1
X2
X8
PZ2
1.3 N
•
m (11.5 lb
•
in)
Series A Cover Shown