Rockwell Automation 20Y PowerFlex 700H, 700S, and 700AFE Drive Fan Systems, Frames 9...14 User Manual
Page 245
Rockwell Automation Publication PFLEX-IN029B-EN-P - August 2014
245
PowerFlex 700AFE Drive - Frame 13 Procedures
Chapter 8
LCL Filter DC Fan Fuses (20-PP20202) Removal and Installation
The LCL filter DC fan fuses are located behind the vented cover at the bottom of
the LCL filter. See
on page
for details.
1.
Review the General Precautions on page
2.
Remove power from the AFE. See Remove Power from the AFE on page
3.
Remove the LCL filter protective covers. See Removing the LCL Filter
Protective Cover in page
4.
Replace the LCL Filter fan fuses.
LCL Filter DC Fan Power Supply (SK-Y1-DCPS1-D1K3 or SK-Y1-DCPS1-E1K0) Removal and
Installation
Note: It is not necessary to remove the fan assembly from the LCL filter, but by
doing so, it may be easier to replace the DC fan power supply circuit board.
The LCL filter DC fan power supply wiring diagram is shown in
Figure 33
. The
diagram shows the connections to the AFE power structure and DC bus.
Figure 33 - LCL Filter Fan DC Power Supply Wiring Diagram
1.
Review the General Precautions on page
2.
Remove power from the AFE. See Remove Power from the AFE on page
IMPORTANT
Use only ATQ8 (Ferraz Shawmut) fuses.
X3
X3
LCL Filter
X8
X53 (3-pin)
+ Pin = DC+ (supply)
- Pin = DC- (supply)
X4
X51 (4-pin)
Pin 5 = +16.5V
Pin 3 = (fan control)
Pin 1 = (fan alarm)
Fuse
X52 (4-pin)
Pin 1 = KLIXON
Pin 4 = KLIXON
X1
Fan
KLIXON
X1
Fan DC Power
Supply PCB
AFE Power Structure
X3 on AFE Power Structure
DC Bus
IMPORTANT
Before doing any work, disconnect the AFE power structure from the AC supply,
and wait until the fan stops and the indicators on the keypad turn off. (If a
keypad is not attached, see the indicator through the keypad base.) Wait 5
more minutes before doing any work on the DC-to-DC power supply. Do not
even open the cover until after this time has expired.