beautypg.com

Rockwell Automation 20Y PowerFlex 700H, 700S, and 700AFE Drive Fan Systems, Frames 9...14 User Manual

Page 233

background image

Rockwell Automation Publication PFLEX-IN029B-EN-P - August 2014

233

PowerFlex 700AFE Drive - Frame 10 Procedures

Chapter 7

8.

Remove the four M5 x10 mm hexalobular screws that secure the fan to the
sheet metal housing and remove the fan. Retain the sheet metal housing
for reuse.

Note: The Main AC and DC fans have different mounting hardware and
hole dimensions. The AC fan uses four M4 x 8 mm screws that are spaced
40 mm apart on the housing. The DC fan uses four M5 x 10 mm screws
that are spaced 65 mm apart on the housing. Based on the manufacturing
date, the sheet metal housing was fabricated for either an AC fan, a DC
fan, or both.

9.

Install the new main DC fan in reverse order. Verify that the fan turns
easily and does not make contact with the sheet metal housing or fan cable
before installing the fan assembly in the AFE.

8

T25
3.5 N

m (31.0 lb

in)

Image for SK-Y1-DCPS2-F10