beautypg.com

Rockwell Automation 20Y PowerFlex 700H, 700S, and 700AFE Drive Fan Systems, Frames 9...14 User Manual

Page 37

background image

Rockwell Automation Publication PFLEX-IN029B-EN-P - August 2014

37

PowerFlex 700H and 700S Drives - Frame 9 Procedures

Chapter 1

5.

Disconnect the stirring fan power wires.

6.

Disconnect the DC supply wire from fan inverter connector X2.

7.

Disconnect the fan supply wire from fan inverter connector X8.

8.

Disconnect the DC fan power supply wire from connector X81

9.

Disconnect the four fuse power wires (black and red pairs) from the top
and bottom of the fuse holder.

10.

Remove the two M5 x 10 mm Phillips head screws that secure the fuse
holder / cooling fan bracket to the frame and left the bracket out of the
drive.

5

6

7

9

8

10

P2
4.0 N

m (35 lb

in)