beautypg.com

Rockwell Automation 20Y PowerFlex 700H, 700S, and 700AFE Drive Fan Systems, Frames 9...14 User Manual

Page 206

background image

206

Rockwell Automation Publication PFLEX-IN029B-EN-P - August 2014

Chapter 7

PowerFlex 700AFE Drive - Frame 10 Procedures

9.

Connect the fan power supply wires to the bottom of the fuse holders.
Note that the red wire (+DC) is connected to the left side terminal and
the black wire (-DC) is connected to the right side terminals.

10.

Install the new main DC fans in the fan housings using the M5 x 10 mm
POZIDRIV screws supplied in the kit. Final torque is 3.5 N

m (31.0

lb

in). See Remove the Main Fan Assembly on page

198

for details.

11.

Remove the backing from the drive modification label and attach the label
to the front of a main fan housing.

12.

Write “DC fan retrofit” and the installation date on the label.

9

Inverter section shown