beautypg.com

Rockwell Automation 20Y PowerFlex 700H, 700S, and 700AFE Drive Fan Systems, Frames 9...14 User Manual

Page 29

background image

Rockwell Automation Publication PFLEX-IN029B-EN-P - August 2014

29

PowerFlex 700H and 700S Drives - Frame 9 Procedures

Chapter 1

Main Fan Fuses (20-PP20202) and Fuse Holder (20-PP20300) Removal
and Installation

The main fan fuses and fuse holder are located on the fan inverter capacitor
bracket below the fan inverter cover.

1.

Review the General Precautions on page

17

.

2.

Remove power from the drive. See Remove Power from the Drive on page

23

.

3.

Remove the lower protective cover from the drive. See Remove the Lower
Protective Cover on
page

24

.

4.

Remove the main fan inverter capacitor bracket. See Removing the Main
Fan Inverter Capacitor Bracket
on page

25

.

5.

Remove and replace the fuses, if necessary. See Checking the Fan Inverter
Fuses on
page

263

.

6.

If, necessary, remove the two M4 x 8 mm POZIDRIV screws that secure
the fuse block to the sheet metal.

7.

Install the fuses and fuse block in the reverse order of removal.

PZ2
3.0 N

m (27 lb

in)

6