ADS Environmental Services Profile Software 950015B6 User Manual
Page 90

2-50
Profile Software User's Guide
CONFIDENTIAL – Covered by ADS Software License Agreement
1998 – 2012 ADS LLC. All Rights Reserved.
the High High Depth Alarm Threshold and Return to 
Normal fields. 
Threshold Enter the flow depth above which you want 
the monitor to contact the IntelliServe system to initiate a 
High High Depth alarm. This value must be zero when 
not in use or at least 2 inches greater than the value entered 
for the High Threshold when it is in use. 
Note: To prevent potential false alarms, input a value 
greater than 1 into the Readings to Average field of the 
Unidepth Averaging section. 
Return to Normal Enter the flow depth below which 
you want the monitor to send a message to the ADS 
IntelliServe system indicating the high, high depth 
conditions no longer exist at the monitor. 
• Low Depth Alarm Set up the following parameters when
you want the FlowShark monitor to send a Low Depth Alarm 
message to an ADS IntelliServe system when specific low 
flow depth conditions occur at the monitor. 
Enable Select this checkbox to enable the Low Depth 
Alarm function using the conditions specified in the Low 
Depth Alarm Threshold and Return to Normal fields. 
Threshold Enter the flow depth below which you want 
the monitor to contact the ADS IntelliServe system to 
initiate a Low Depth alarm. This depth should be lower 
than the lowest depth that commonly occurs at the 
location. 
Note: To prevent potential false alarms, input a value 
greater than 1 into the Readings to Average field of the 
Unidepth Averaging section. 
Return to Normal Enter the flow depth at which you 
want the monitor to send a message to the ADS 
IntelliServe system indicating the low depth conditions no 
longer exist at the monitor. 