Analog input device (flowshark) – ADS Environmental Services Profile Software 950015B6 User Manual
Page 69

Profile Main Screen
2-29
CONFIDENTIAL – Covered by ADS Software License Agreement
1998 - 2012 ADS LLC. All Rights Reserved.
• Input Type Select the range for the signal. Profile defaults
to 4 to 20 mA.
• Min Scale Enter the data value corresponding to the lowest
signal in the range. Profile defaults this scale to 0.
• Max Scale Enter the data value corresponding to the highest
signal in the range. You must set the maximum scale about 0
to use this device. Profile defaults this scale to 0.
• Store Data Select this checkbox to ensure that the monitor
logs the data produced through this device. The monitor saves
the data by default (selected).
Analog Input Device (FlowShark)
Edit the analog input device associated with a FlowShark monitor in
the following way:
Edit Analog Input Device (FlowShark)
• Entity Select the entity for which you want to input data
through the analog input.
• Min Value Enter the reading you want to correspond to 4
mA.
• Max Value Enter the reading you want to correspond to 20
mA.