Dc common bus configurations, Table 56 - iam module terminology and use, Figure 42 - typical dc common-bus configuration – Rockwell Automation 2094-xMxx-S Kinetix 6000 Multi-axis Servo Drives User Manual User Manual

Page 86: N.c. n.c. n.c

background image

86

Rockwell Automation Publication 2094-UM001H-EN-P - June 2013

Chapter 5

Connecting the Kinetix 6000 Drive System

DC Common Bus
Configurations

When the IAM module is used in a DC common-bus configuration, the IAM
module is known as a leader IAM or follower IAM module. The IAM (non-
common bus) and leader IAM module have identical three-phase input power
connections. The leader IAM module is responsible for discharging the DC bus,
and for providing common-bus follower drives with DC bus pre-charge, bus
regulation, phase-loss detection, and ground fault detection. Follower IAM
modules do not have three-phase input power connections, but have DC bus
connections from a leader IAM module.

Table 56 - IAM Module Terminology and Use

The Kinetix 6000 leader IAM module can operate with non-Kinetix 6000
follower drives, as can the Kinetix 6000 follower IAM module operate with non-
Kinetix 6000 common-bus leader drives. However, non-Kinetix 6000 leader and
follower drives must meet the same functional requirements as the Kinetix 6000
leader and follower IAM modules.

Figure 42 - Typical DC Common-bus Configuration

This Module

Is Wired

And is

IAM

With three-phase input power.

Not wired in Common-bus mode.

Leader IAM

With three-phase input power, but has DC common-bus
connections to a follower IAM module.

Wired in Common-bus mode.

Follower IAM

Without three-phase input power, but has DC common-bus
connections from a leader IAM module.

Wired in Common-bus mode and configured by
using the Logix Designer application.

IMPORTANT

Use Kinetix 6000 drive firmware revision 1.85 and the Logix Designer
Application or RSLogix 5000 software, version 15 or later, for common-bus
power configurations.

IMPORTANT

Any non-Kinetix 6000 common-bus leader IAM module that does not provide
pre-charge is required to add an additional external pre-charge circuit before
connecting to any Kinetix 6000 common-bus follower IAM module.

DC-

DC+

L3

L2

L1

CONT EN-

CONT EN+

W

V

U

MBRK -

MBRK +

COM

PWR

DBRK -

DBRK +

CTRL 2

CTRL 1

1 2 3 4

1 2 3 4 5 6

1 2

1 2 3 4 5 6

1 2

W

V

U

MBRK -

MBRK +

COM

PWR

DBRK -

DBRK +

1 2 3 4

1 2 3 4 5 6

W

V

U

MBRK -

MBRK +

COM

PWR

DBRK -

DBRK +

1 2 3 4

1 2 3 4 5 6

DC-

DC+

L3

L2

L1

CONT EN-

CONT EN+

W

V

U

MBRK -

MBRK +

COM

PWR

DBRK -

DBRK +

CTRL 2

CTRL 1

1 2 3 4

1 2 3 4 5 6

1 2

1 2 3 4 5 6

1 2

W

V

U

MBRK -

MBRK +

COM

PWR

DBRK -

DBRK +

1 2 3 4

1 2 3 4 5 6

W

V

U

MBRK -

MBRK +

COM

PWR

DBRK -

DBRK +

1 2 3 4

1 2 3 4 5 6

N.C.
N.C.
N.C.

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

BAUD

RATE

TX

RX

DPI

BAUD

RATE

TX

RX

BAUD

RATE

TX

RX

BAUD

RATE

TX

RX

DPI

BAUD

RATE

TX

RX

BAUD

RATE

TX

RX

2094-xCxx-Mxx-x

Common-bus Leader

IAM Module

2094-xMxx-x AM Modules or

2094-SEPM-B24-S IPIM Modules

Bonded Cabinet
Ground

Three-phase

Input Power

Kinetix 6000

DC Common Bus

Connections

2094-xCxx-Mxx-x

Common-bus Follower

IAM Module

2094-xMxx-x AM Modules or

2094-SEPM-B24-S IPIM Modules