Write the new idn parameter value – Rockwell Automation 2094-xMxx-S Kinetix 6000 Multi-axis Servo Drives User Manual User Manual
Page 253

Rockwell Automation Publication 2094-UM001H-EN-P - June 2013
253
Changing the Default IDN Parameter Values
Appendix E
Write the New IDN Parameter Value
Follow these steps to write the new IDN parameter value.
1. Configure a Message Configuration (MSG) instruction to write the IDN
parameter value required for your application.
In this example, the Message Configuration (MSG) instruction is set to
write the additional bus capacitance of your leader IAM power module.
a. From the Message Type pull-down menu, choose sercos IDN Write.
b. From the Identification Number pull-down menus, choose P-0-99.
2. Click New Tag.
3. The New Tag dialog box opens.
4. Type the name of your Source tag.
In this example, the tag name is Write_Value.
5. Click OK.
In this example, the new tag creates a source value (that you entered) that
the MSG instruction uses to overwrite the existing P-0-099 IDN value.