beautypg.com

Rockwell Automation 2094-xMxx-S Kinetix 6000 Multi-axis Servo Drives User Manual User Manual

Page 258

background image

258

Rockwell Automation Publication 2094-UM001H-EN-P - June 2013

Appendix F

Enhanced Peak Performance

4. Overwrite the existing TorqueLimitPositive and TorqueLimitNegative

values.

In this example, the calculated values are 178.1 and -178.1 (respectively).

The calculated value for Torque

max

is the maximum value for the

following:

TorqueLimitBipolar
TorqueLimitPositive (+)
TorqueLimitNegative (-)

If you want to limit the torque, adjust the calculated values to a value closer
to zero. The values shown are the default values for 150% peak torque with
this motor and drive pair.

5. Click the Output tab.

The TorqueScaling and LoadInertiaRatio values are populated after an
autotune. If an autotune is not possible, model the system in Motion
Analyzer software and enter that value for the LoadInertiaRatio. The
default value for the LoadInertiaRatio is 0.0, however for this example, a
ratio of 10.20:1 is used (load inertia = 0.015 Kg-m^2).

To calculate the maximum acceleration and deceleration from Torque

max

,

use this equation.

TIP

For more information on system configuration with your Logix5000
controller and the Logix Designer application, refer to

page 133

.

Default LoadInertiaRatio Value

Default TorqueScaling Value

IMPORTANT

To obtain more accurate results, performing Autotune in the Logix
Designer application is recommended.

Torque

max

100

Accel

max

=

TorqueScaling

TIP

If autotune cannot be performed, enter the data for the
LoadInertiaRatio, DriveResolution, and ConversionConstant as shown
in

step 5

through

step 9

.