Calculate total bus capacitance – Rockwell Automation 2094-xMxx-S Kinetix 6000 Multi-axis Servo Drives User Manual User Manual
Page 226
226
Rockwell Automation Publication 2094-UM001H-EN-P - June 2013
Appendix C
DC Common Bus Applications
Calculate Total Bus
Capacitance
Total bus capacitance is the sum of all capacitance values for your Bulletin 2094
common-bus modules. Specifically, this includes the capacitance values for each
of these modules:
• Leader IAM (converter and inverter) module
• Each AM and shunt module (if present) on the leader IAM power rail
• Each IPIM module (if present) on the leader IAM power rail
• Each follower IAM (converter and inverter) module
• Each AM module on the follower IAM power rail
• Each IPIM module (if present) on the follower IAM power rail
Refer to Bulletin 2094 Drive Capacitance Values on
for IAM, AM,
IPIM, and shunt module capacitance values.
Table 116 - Maximum IAM Module Bus Capacitance
IMPORTANT
If total bus capacitance of your system exceeds the leader IAM module pre-
charge rating and input power is applied, the IAM module seven-segment
status indicator displays error code E90 (pre-charge timeout fault).
To correct this condition, you must replace the leader IAM module with a larger
module or decrease the total bus capacitance by removing AM modules or IPIM
modules.
Leader IAM (200V-class)
Module
Bus Capacitance,
max
μF
Leader IAM (400V-class)
Modules
Bus Capacitance,
max
μF
2094-AC05-MP5-x
7145
2094-BC01-MP5-x
4585
2094-AC05-M01-x
2094-BC01-M01-x
2094-AC09-M02-x
15,295
2094-BC02-M02-x
8955
2094-AC16-M03-x
34,400
2094-BC04-M03-x
8955
2094-AC32-M05-x
62,825
2094-BC07-M05-x
17,915
IMPORTANT
If your total bus capacitance value exceeds the value in the table above, you
must increase the size of the leader IAM module or decrease the total bus
capacitance by removing other modules on the power rail.