Rockwell Automation Publication 2094-UM001H-EN-P - June 2013

Chapter 8

Removing and Replacing the Kinetix 6000 Drive Modules

Remove Kinetix 6000 Drive
Modules

Follow these steps to remove the IAM, AM, and IPIM modules from the
Bulletin 2094 power rail.

1. Verify that all control and input power has been removed from the system.

2. Wait five minutes for the DC bus to discharge completely before

proceeding.

3. Label and remove all connectors from the IAM/AM module you are

removing.

To identify each connector, refer to

page 58

.

4. Remove the motor cable from the cable shield clamp, as shown in these

examples.

5. Loosen the mounting screw (bottom center of each module).
6. Grasp the top and bottom of the module with both hands and gently pull

the module away from the connectors enough to clear the guide pins
(module pivots on top bracket).

ATTENTION: To avoid shock hazard or personal injury, assure that all
power has been removed before proceeding. This system can have
multiple sources of power. More than one disconnect switch can be
required to de-energize the system.

ATTENTION: This product contains stored energy devices. To avoid
hazard of electrical shock, verify that all voltage on capacitors has been
discharged before attempting to service, repair, or remove this unit. Do
not attempt the procedures in this document unless you are qualified
to do so and are familiar with solid-state control equipment and the
safety procedures in publication NFPA 70E.

Use screwdriver with

3.5 mm (0.14 in.) tip to depress

spring and remove cable.

Slide-open

Cable Clamp

Screwdriver Tip in Slot

Vertical Cable Clamp

Orientation Example

Cable Clamp

Motor
Cable

Vent Holes on Top of IAM/AM Module

Horizontal Cable Clamp

Orientation Examples

Pivot-open

Cable Clamp

Pry back
with thumb.