Rockwell Automation 2094-xMxx-S Kinetix 6000 Multi-axis Servo Drives User Manual User Manual
Page 49

Rockwell Automation Publication 2094-UM001H-EN-P - June 2013
49
Planning the Kinetix 6000 Drive System Installation
Chapter 2
When mounting your shunt module inside the enclosure, follow these additional
guidelines:
• Mount metal-clad modules anywhere in the dirty zone, but as close to the
Bulletin 2094 drive system as possible.
• Route shunt power wires with motor power cables.
• Keep unshielded wiring as short as possible. Keep shunt wiring as flat to
the cabinet as possible.
• Separate shunt power cables from other sensitive, low voltage signal cables.
Figure 20 - External Shunt Module Inside the Enclosure
C
D
D
D
D
D
VD
C
VD
1394 Digital Servo Controller
300W Shunt Module
BULLETIN 1394 300W SHUNT MODULE
ALLEN-BRADLEY
FOR USE WITH 1394-SJT22-X SYSTEM MODULE
CAT.
PART
SER.
INPUT DC
INPUT AC
FOR FUSE REPLACEMENT USE:
BUSSMAN CAT. NO.
R
D
Line Interface Module
Kinetix 6000
System
Dirty Wireway
Clean Wireway
Motor Power Cables
Enclosure
2094-BSP2
Shunt Module
I/O and Feedback Cables
150 mm (6.0 in.)
clearance (min) on all four
sides of the shunt module.
Shunt thermal Switch and Fan Wires (when present)
Very Dirty Connections Segregated
(not in wireway)
Shunt Power Wiring Methods:
Twisted pair in conduit (1st choice).
Shielded twisted pair (2nd choice).
Twisted pair, two twists per foot (min) (3rd choice).
No sensitive
equipment within
150 mm (6.0 in.).
Route 24V DC I/O
shielded cable.
Route encoder/analog/registration
shielded cables.