2.7.1 SINGLE +24 V DC POWER SOURCE TO CONTROLLER AND ITBS

The procedure to connect the controller TB2 screw lugs to a +24 V dc power source is provided in
Table 2-3. This procedure assumes the power supply, controller, and ITBs are negatively
grounded (negative ground system).

Table 2-3. Single +24 V dc Power Source to Controller and ITBs

Step

Procedure

See Figure

1

Connect the positive (+) 24 V input line, via a remote SPST switch, to TB2-4
(

L1).

Figure 2-13

2

Connect the negative (-) 24 V input line to TB2-3 (

L2).

Figure 2-13

3

Connect TB2-1, Power Common (

PC), to a bus bar that is connected to

earth ground.
Individual wires should connect each controller Power Common (

PC) screw

lug to the common bus bar.

Figure 2-13

Figure 2-14

4

Connect the earth ground to TB2-5, Chassis Safety Ground (

G).

Figure 2-13

Figure 2-13. Single +24 V dc Power Source to Controller and ITBs

1 2 3 4 5

PC L3 L2 L1 G

SPST

24 V dc

POWER

SUPPLY

-

+

EARTH GROUND

TB2 (REAR OF
CONTROLLER)

AC

COMMON BUS BAR FOR

ALL CONTROLLERS

53MC5000 Process Control Station